Main And Control Circuit Wiring - Omron V1000 Guía Rápida De Referencia

Ocultar thumbs Ver también para V1000:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 64
3 Electrical Installation

Main and Control Circuit Wiring

Wiring the Main Circuit Input
Consider the following precautions for the main circuit input.
• Use only circuit breakers that have been designed specifically for drives.
• If using a ground fault circuit breaker, make sure that it can detect both DC and
high frequency current.
• If using an input switch is used, make sure that the switch does not operate not
more than once every 30 minutes.
• Use a DC reactor or AC reactor on the input side of the drive:
• To suppress harmonic current.
• To improve the power factor on the power supply side.
• When using an advancing capacitor switch.
• With a large capacity power supply transistor (over 600 kVA).
Wiring the Main Circuit Output
Consider the following precautions for the output circuit wiring.
• Do not connect any other load than a 3 phase motor to the drives output.
• Never connect a power source to the drives output.
• Never short or ground the output terminals.
• Do not use phase correction capacitors.
• If using a contactor between the drive and motor, it should never be operated
when the drive is outputting a voltage. Operating while there is voltage output can
cause large peak currents, thus tripping the over current detection or damage the
drive.
Ground Connection
Take the following precautions when grounding the drive.
• Never share the ground wire with other devices such as welding machines, etc.
• Always use a ground wire, that complies with electrical equipment technical stan-
dards. Keep ground wires as short as possible. Leakage current is caused by the
drive. Therefore, if the distance between the ground electrode and the ground termi-
nal is too long, potential on the ground terminal of the drive will become unstable.
• When using more than one drive, do not to loop the ground wire.
Control Circuit Wiring Precautions
Consider the following precautions for wiring the control circuits.
• Separate control circuit wiring from main circuit wiring and other high-power lines.
• Separate wiring for control circuit terminals MA, MB, MC (contact output) from wir-
ing to other control circuit terminals.
12
I67E-EN
V1000 Quick Start Guide

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido