Malfunction
A valve LED does
not light up.
Air is audibly
escaping.
VS does not
exhaust air.
Valve does not switch. One or both of the manual overrides is
AVENTICS | CD01-PI | R412012449–BAL–001–AD
Possible cause
Valve is defective.
Incorrect channel is controlled.
Electric connections are defective.
Seal is missing or damaged.
Component is leaking.
End plate exhaust is closed
Pressure zone separators are
incorrectly mounted.
in position "1".
13 Technical data
Please visit our online catalog
(www.aventics.com/pneumatics-catalog)
for technical data.
Remedy
Replace valve.
Check the control.
Check the electric connections and
replace if necessary.
Check the seal and replace if
necessary.
Replace component.
Open the exhaust and connect a
silencer or a line for restricted exhaust.
Check the pressure zone separators
and remove if necessary.
Handhilfsbetätigungen auf Position "0"
stellen.
95