5.2 PARÁMETROS DEL PRODUCTO
e) PROTOCOLE «DNP»
!
RUTA: SETTINGS
PRODUCT SETUP
# DNP PROTOCOL
#
5
5-12
!"
COMMUNICATIONS
DNP PORT:
NONE
DNP ADDRESS:
MENSAJE
255
# DNP NETWORK
MENSAJE
# CLIENT ADDRESSES
DNP TCP/UDP PORT
MENSAJE
NUMBER: 20000
DNP UNSOL RESPONSE
MENSAJE
FUNCTION: Disabled
DNP UNSOL RESPONSE
MENSAJE
TIMEOUT: 5 s
DNP UNSOL RESPONSE
MENSAJE
MAX RETRIES: 10
DNP UNSOL RESPONSE
MENSAJE
DEST ADDRESS: 1
USER MAP FOR DNP
MENSAJE
ANALOGS: Disabled
NUMBER OF SOURCES
MENSAJE
IN ANALOG LIST: 1
DNP CURRENT SCALE
MENSAJE
FACTOR: 1
DNP VOLTAGE SCALE
MENSAJE
FACTOR: 1
DNP POWER SCALE
MENSAJE
FACTOR: 1
DNP ENERGY SCALE
MENSAJE
FACTOR: 1
DNP OTHER SCALE
MENSAJE
FACTOR: 1
DNP CURRENT DEFAULT
MENSAJE
DEADBAND: 30000
DNP VOLTAGE DEFAULT
MENSAJE
DEADBAND: 30000
DNP POWER DEFAULT
MENSAJE
DEADBAND: 30000
DNP ENERGY DEFAULT
MENSAJE
DEADBAND: 30000
DNP OTHER DEFAULT
MENSAJE
DEADBAND: 30000
DNP TIME SYNC IIN
MENSAJE
PERIOD: 1440 min
M60 relé para protección de motor
!"
DNP PROTOCOL
Rango: NONE, COM1 - RS485, COM2 - RS485, FRONT
PANEL - RS232, NETWORK
Rango: 0 a 65519 en pasos de 1
Rango: Presione la tecla MESSAGE
dirección DNP del cliente de red.
Rango: 1 a 65535 en pasos de 1
Rango: Enabled (Activado), Disabled (Desactivado)
Rango: 0 a 60 s en pasos de 1
Rango: 1 a 255 en pasos de 1
Rango: 0 a 65519 en pasos de 1
Rango: Enabled, Disabled
Rango: 1 a 4 en pasos de 1
Rango: 0.01. 0.1, 1, 10, 100, 1000
Rango: 0.01. 0.1, 1, 10, 100, 1000
Rango: 0.01. 0.1, 1, 10, 100, 1000
Rango: 0.01. 0.1, 1, 10, 100, 1000
Rango: 0.01. 0.1, 1, 10, 100, 1000
Rango: 0 a 65535 en pasos de 1
Rango: 0 a 65535 en pasos de 1
Rango: 0 a 65535 en pasos de 1
Rango: 0 a 65535 en pasos de 1
Rango: 0 a 65535 en pasos de 1
Rango: 1 a 10080 min. en pasos de 1
5 AJUSTES
!
para ingresar la
GE Multilin