8 Diagnosis, asset management and service
Code
Reason
Text message
•
F017
Adjustment
not within
Adjustment span
specification
too small
•
F025
Index markers
are not conti-
Error in the line-
nuously rising,
arization table
for example
illogical value
pairs
•
F040
Hardware
defect
Error in the elec-
tronics
•
F080
General soft-
ware error
•
F105
The instrument
is still in the
Determine mea-
start phase,
sured value
the measured
value could
not yet be
determined
•
F113
EMC interfe-
rence
Communication
error
•
F125
Temperature
of the elect-
Impermissible
ronics in the
electronics tem-
non-specified
perature
range
•
F260
Error in the
calibration
Error in the cali-
carried out in
bration
the factory
•
Error in the
EEPROM
32
Removal
Code
Text message
•
Change
F261
adjustment
Error in the con-
according to
figuration
the limit values
(difference
between min.
and max.
≥ 10 mm)
•
Check lineari-
F264
zation table
Installation/Se-
•
Delete table/
tup error
Create new
•
Exchanging
the electronics
•
Send instru-
ment for repair
F265
•
Measurement
Disconnect
function distur-
operating vol-
bed
tage briefly
•
Wait for the
end of the
switch-on
Function check
phase
•
The following table shows the error codes and
Duration
depending on
text messages in the status message "Function
the version
check" and provides information on causes as
and parameter
well as corrective measures.
adjustment up
to approxi-
Code
mately 3 min.
Text message
•
Remove EMC
C700
influences
Simulation ac-
tive
•
Check ambient
temperature
Out of specification
The following table shows the error codes and
text messages in the status message "Out of
•
Exchanging
specification" and provides information on cau-
the electronics
•
ses as well as corrective measures.
Send instru-
ment for repair
Code
Text message
S600
Impermissible
electronics tem-
perature
Reason
Removal
•
•
Error during
Repeat setup
•
setup
Repeat reset
•
False signal
suppression
faulty
•
Error when
carrying out a
reset
•
•
Adjustment
Check or
not within the
correct ins-
vessel height/
tallation and/
measuring
or parameter
range
adjustment
•
•
Max. measu-
Use an instru-
ring range of
ment with big-
the instrument
ger measuring
not sufficient
range
•
•
Sensor no
Check opera-
longer carries
ting voltage
•
out a measure-
Carry out a
ment
reset
•
•
Operating vol-
Disconnect
tage too low
operating vol-
tage briefly
Reason
Removal
•
•
A simulation is
Finish simu-
active
lation
•
Wait for the
automatic end
after 60 mins.
Reason
Removal
•
•
Temperature
Check ambient
of the elect-
temperature
ronics in the
non-specified
range
VEGAPULS WL S 61 • 4 ... 20 mA