Mounting Versions; Mounting Instructions - Vega VEGAPULS WL S 61 Manual De Instrucciones

Ocultar thumbs Ver también para VEGAPULS WL S 61:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

These are mainly:
Active measuring component
Process fitting
Process seal
Process conditions are particularly:
Process pressure
Process temperature
Chemical properties of the medium
Abrasion and mechanical influences
You can find detailed information on the process
conditions in chapter "Technical data" as well as
on the type label.
4.2

Mounting versions

Straining clamp
Most simply mount the instrument via the
straining clamp. For this purpose, the connec-
tion cable is provided with a strain relief wire of
Kevlar.
In order to avoid faulty measured values, make
sure that the sensor does not oscillate.
> 200 mm
Abb. 20: Mounting via a straining clamp
Mounting bracket
For a rigid mounting, a mounting bracket with
opening for thread G1½, e.g. from the VEGA
product range, is recommended. The mounting
of the sensor in the bracket is carried out via a
G1½ counter nut of plastic. Take note of chapter
"Mounting instructions" for the distance to the
wall.
VEGAPULS WL S 61 • 4 ... 20 mA
(7.87")
> 200 mm
Abb. 21: Mounting via a mounting bracket
4.3

Mounting instructions

Polarisation
The emitted radar impulses of the radar sensor
are electromagnetic waves. The polarisation is
the direction of the electrical wave component.
By turning the instrument in the mounting strap,
the polarisation can be used to reduce the
effects of false echoes.
The position of the polarisation is in the middle
of the type label on the instrument.
Abb. 22: Position of the polarisation
1
Middle of the type label
Inflowing medium
Do not mount the instrument in or above the
filling stream. Make sure that you detect the
product surface, not the inflowing product.
Abb. 23: Mounting of the radar sensor with inflowing
medium
4 Mounting
(7.87")
1
27