Rectify Faults - Vega VEGAPULS WL S 61 Manual De Instrucciones

Ocultar thumbs Ver también para VEGAPULS WL S 61:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Code
Reason
Text message
S601
Danger of ves-
sel overfilling
Overfilling
Maintenance
The following table shows the error codes and
text messages in the status message "Mainte-
nance" and provides information on causes as
well as corrective measures.
Code
Reason
Text message
M500
With the reset
to delivery
Error with the
status, the
reset delivery
data could not
status
be restored
M501
Hardware error
EEPROM
Error in the
non-active linea-
rization table
M502
Hardware error
EEPROM
Error in the diag-
nosis memory
M503
The echo/
noise ratio is
Meas. reliability
too small for
too low
reliable mea-
surement
M504
Hardware
defect
Error on an de-
vice interface
M505
Level echo can
no longer be
No echo availa-
detected
ble
VEGAPULS WL S 61 • 4 ... 20 mA
8.4
Removal
Reaction when malfunction occurs
The operator of the system is responsible for
Make sure
that there is no
taking suitable measures to rectify faults.
further filling
Check level in
Procedure for fault rectification
the vessel
The first measures are:
Further comprehensive diagnostics options
are available with a PC with PACTware and the
Removal
suitable DTM. In many cases, the reasons can
be determined in this way and faults rectified.
Repeat reset
Check the 4 ... 20 mA signal
Load XML file
Connect a multimeter in the suitable measuring
with sensor
range according to the wiring plan. The following
data into the
table describes possible errors in the current
sensor
signal and helps to eliminate them:
Send instru-
ment for repair
Error
4 ... 20 mA
signal not
Send instru-
stable
ment for repair
4 ... 20 mA
Check
signal mis-
installation
sing
and process
conditions
Clean the
antenna
Change
polarisation
direction
Check con-
nections
Send instru-
ment for repair
Clean the
antenna
Remove
Current sig-
possible false
nal greater
echoes
than 22 mA
Optimize sen-
or less than
sor position
3.6 mA
and orientation
Reaction after fault rectification
Depending on the reason for the fault and the
measures taken, the steps described in chapter
"Setup" must be carried out again or must be
8 Diagnosis, asset management and service

Rectify faults

Evaluation of fault messages via the adjust-
ment instrument
Checking the output signal
Treatment of measurement errors
Reason
Fluctu-
ations
of the
measured
variable
Electrical
connec-
tion faulty
Voltage
supply
missing
Operating
voltage
too low
or load
resistance
too high
Elect-
ronics
module in
the sensor
defective
Removal
Set damping approp-
riate to the instrument
via the display and
adjustment module or
PACTware/DTM
Check connection
according to chapter
"Connection steps" and
if necessary, correct
according to chapter
"Wiring plan"
Check cables for
breaks; repair if neces-
sary
Check, adapt if neces-
sary
Exchange the instru-
ment or send it in for
repair
33