RME: Relay minimum enable time. Specifies the minimum amount of time the relay
should be enabled.
RDD: Relay disable delay. Specifies the amount of time the relay disable condition
must be present before acting upon it.
Al:
Alarm low voltage. When the battery voltage falls below this value for more than
10 seconds the low voltage alarm is turned on. This is a visual and audible alarm.
It does not activate the relay.
Alc:
Clear low voltage alarm. When the battery voltage rises above this value, the
alarm is turned off. This value needs to be greater than or equal to Al.
Ah:
Alarm high voltage. When the battery voltage rises above this value for more
than 10 seconds the high voltage alarm is turned on. This is a visual and audible
alarm. It does not activate the relay.
Ahc:
Clear high voltage alarm. When the battery voltage falls below this value, the
alarm is turned off. This value needs to be less than or equal to Ah.
Alarm low SOC. When the state-of-charge falls below this value for more than 10
AS:
seconds the low SOC alarm is turned on. This is a visual and audible alarm. It
does not activate the relay.
Clear low SOC alarm. When the state-of-charge rises above this value, the alarm
ASc:
is turned off. This value needs to be greater than or equal to AS.
A BUZ:
When set, the buzzer will sound on an alarm. After a button is pressed the
buzzer will stop sounding. When not enabled the buzzer will not sound on an
alarm condition.
Rl:
Relay low voltage. When the battery voltage falls below this value for more than
10 seconds the alarm relay will be activated.
Rlc:
Clear relay low voltage. When the battery voltage rises above this value, the
relay will be de-activated. This value needs to be greater than or equal to Rl.
Rh:
Relay high voltage. When the battery voltage rises above this value for more
than 10 seconds the relay will be activated.
Rhc:
Clear relay high voltage. When the battery voltage falls below this value, the
relay will be de-activated. This value needs to be less than or equal to Rh.
SA:
Maximum rated shunt current. If using a shunt other than the one supplied with
the BMV, set to the rated current of the shunt.
SV:
Shunt voltage at the maximum rated current. If using a shunt other than the
one supplied with the BMV, set to the rated voltage of the shunt.
BL I:
Intensity backlight. The intensity of the backlight, ranging from 0 (always off) to 9
(maximum intensity).
BL ON: Backlight always on. When set the backlight will not automatically turn off after
20 seconds of inactivity.
D V:
Battery voltage display. Should be ON to display battery voltage in the monitoring
menu.
D I:
Current display. Should be ON to display current in the monitoring menu.
D CE: Consumed Ah display. Should be ON to display consumed Ah in the monitoring
menu.
D SOC: State-of-charge display. Should be ON to display state-of-charge in the
monitoring menu.
D TTG: Time-to-go display. Should be ON to display time-to-go in the monitoring menu.
ZERO: Zero current calibration. If the BMV reads a non-zero current even when there is
no load and the battery is not being charged, this option can be used to calibrate the
zero reading. Ensure that there really is no current flowing into or out of the battery,
then hold the select button for 3 seconds.
11