Preparation for installing the unit
5.8. Battery cabling length
The inverter measures the battery voltage in its connection terminals. For this reason, the installer must use a DC
cable with a sufficiently low impedance to prevent the battery charge/discharge process from causing the unit to
disconnect due to high or low battery voltage (see section "8.2. Wiring requirements for connecting the storage
system").
5.9. Auxiliary grid/genset cabling length
The inverter measures the grid/genset voltage in its connection terminals. For this reason, the installer must use
an AC cable with a sufficiently low impedance to prevent the current absorption/injection from causing the unit
to disconnect due to high or low grid voltage (see section "10.2. Wiring requirements for connecting the auxiliary
grid/genset").
5.10. Photovoltaic panels
The photovoltaic panels of the installation must be Class A (IEC 61730). These units do not admit photovoltaic
panel grounding, therefore the PV array terminals must be isolated from ground. Otherwise the inverter will give an
insulation fault.