Logic 1: either the heat pump or the optional electric heater can be started at the same time.
Logic 2: both the heat pump and the optional electric heater can be started at the same time after the
compressor has run for four minutes and T

2.4.8 Remote Sensor

[Operation Instructions]
At the commissioning parameter setting page, by touching "Remote sensor", the control panel will access to the
corresponding setting page, where it can be set to "With" or "Without".
[Notes]
●This setting will be memorized upon power failure.
●Only when "Remote sensor" is set to "With", the "Ctrl. State" can be set to "T-room".
2.4.9 Air Removal
[Operation Instructions]
At the commissioning parameter setting page, by touching "Air removal", the control panel will access to the
corresponding setting page, where it can be set to "On" or "Off".
[Notes]
● This setting will be memorized upon power failure.
● This setting can be done only when the unit is turned off. And when it is set to "On", the unit is not allowed to
be turned on.
2.4.10 Floor Debug
[Operation Instructions]
1. At the commissioning parameter setting page, by touching "Floor debug", the control panel will access to the
corresponding setting page.
2. At the setting page, "Floor debug", "Segments", "Period 1 temp", "Segment time", and "ΔT of segment"
can be set.
No.
Full Name
1
Floor debug switch
is equal to or lower than WOT-heat–Δt2.
Optional Water Temp
Displayed Name
Range
Floor debug
On/Off
20
Operation Instructions for Versati III
Default
Accuracy
Off
/