2.8
SAFETY KIT
Safety kit assembly is mandatory.
The kit code 8101524 supplied as option
for "DEWY EQUIPE P100-200-300-400
BOX" models it is formed (fig. 7):
– System supply flanged section code
6291970
– System return flanged section code
6291968
– Gaskets, nuts and fastening screws M16
– Thermomet er 0-120° C 1/2" code
6146004
– 4.5 BAR safety valve code 6042206
and drain funnel code 6269403
– Safety thermostat 100°C manual reset
code 6001409
– 5 BAR 1/4" water pressure switch code
6037550
– 0-10 BAR 1/4" pressure gauge code
6217051, tap cod. 6216606 and lock
code 6216650
– Expansion vessel 8 liters code 6245108,
connection pipe code 6227661, gaskets
and nipple.
WARNING: In models "P100-200-300-
400 BOX" the safety kit can be inserted
in a specif ic pr o t ective case code
8101527 supplied separately.
The kit code 8101525 supplied as option
for "DEWY EQUIPE P500-600 BOX"
models it is formed (fig. 7/a):
– System supply flanged section code
6291969
– System return flanged section code
6291971
– Gaskets, nuts and fastening screws M16
– Thermomet er 0-120° C 1/2" code
6146004
– 4.5 BAR safety valve code 6042206
and drain funnel code 6269403
– Safety thermostat 100°C manual reset
code 6001409
– 5 BAR 1/4" water pressure switch code
6037550
– 0-10 BAR 1/4" pressure gauge code
6217051, tap code 6216606 and lock
code 6216650
– Expansion vessel 8 liters code 6245108,
connection pipe code 6227661, gaskets
and nipple.
WARNING: In models "P500-600 BOX"
the safety kit can be inserted in a specific
protective case code 8101527 supplied
separately.
Capillar y assembly of fuel
on/of f valve calibrated to
98°C, not supplied.
ATTENTION: Safety kit assembly
is mandatory.
ATTENTION: Safety kit assembly
is mandatory.
Assembly of the capillary of
the qualified fuel cut off valve,
calibrated at 98°C, supplied
as option.
IT
ES
GB
Fig. 7
Fig. 7/a
67