INSTALLATION

IT
ES
Installation is permanent and must exclu-
sively be performed by specialised and
qualified personnel, following all the
GB
instructions and provisions included in
this manual.
Current regulations must also be met.
2. 1
SUPPLY
"DEWY EQUIPE P100 and 200 BOX" heat
modules, inter-connectible by flange, are
supplied with an external pre-painted zinc-
coated laminate case.
They are complete with supply/return
water manifold fastening screws and
gaskets and sequence/cascade digestion
unit code 8096301 supplied with "P100-
200-300-400 BOX" modules and code
8096308 supplied with "500-600 BOX"
modules.
Available separately:
– Safety kit cod. 8101524 for modules
"P100-200-300-400 BOX" and cod.
8101525 for modules "P500-600 BOX"
– Double box (size: 1100 x 790 x 1600) for
hydraulic separator/safety kit and distri-
butors, code 8101527 (figure 4)
– Hydraulic separator kit cod. 8101552
for modules "P100-200-300-400 BOX"
and code 8101553 for modules "P500-
600 BOX"
FOR MODULES "P100-200-300-400 BOX"
PER MODULI "P100-200-300-400 BOX"
E "P160-260-360 BOX"
1100
62
– Polypropylene exhaust manifold kit for
indoor installation (purposely treated to
resist weathering when installed out-
doors):
code 8102510 for "P100 BOX" module
code 8102530 for "P200 BOX" module
code 8102531 for "P300 BOX" module
code 8102532 for "P400 BOX" module
code 8102533 for "P500 BOX" module
code 8102534 for "P600 BOX" module
– Exhaust terminal code 8089530 for out-
door installations.
To electrically connect the modules and to
assemble the exhaust for indoor or outdoor
installations, see points 2.6, 2.7 and 2. 1 0 in
this manual.
2.2
INSTALLATION
2.2. 1
Indoors
"DEWY EQUIPE P100-200-300-400-500-
600 BOX" heat modules can be installed in
boiler rooms whose size and requirements
meet current regulations.
Furthermore, vents, with surface areas at
least 3.000 sq. cm or 5.000 sq. cm for
gas with density over 0.8, must be installed
in the outer walls for room ventilation.
396
790
NOTE: move the flanges fixed to the box wall with screws and place them in the
location shown in the figure, depending on the type of hydraulic separator used.
2.2.2
Outdoors
"DEWY EQUIPE P100-200-300-400-500-
600 BOX" heat modules can also be instal-
led outdoors with the specific exhaust for
single module code 8089530.
2.3
SYSTEM CONNECTIONS
To protect the heat system from damaging
corrosion, incrustation or deposits, after
installation it is extremely important to clean
the system using suitable products such as,
for example, Sentinel X300 (new systems),
X400 and X800 (old systems) or Fernox
Cleaner F3. Complete instructions are pro-
vided with the products but, for further infor-
mation, you may directly contact SENTINEL
PERFORMANCE SOLUTIONS LTD or FER-
NOX COOKSON ELECTRONICS. For long-
term protection agains corrosion and depo-
sits, the use of inhibitors such as Sentinel
X100 or Fernox Protector F1 is recom-
mended after cleaning the system. It is
important to check the concentration of the
inhibitor after each system modification and
during maintenance following the manufac-
turer's instructions (specific tests are availa-
ble at your dealer). The safety valve drain
must be connected to a collection funnel to
collect any discharge during interventions.
FOR MÓDULES "P500-600 BOX"
PER MODULI "P500-600 BOX"
E "P460-560 BOX"
396
Fig. 4