4.6 Alarms management

4.6.1
Digital input alarms
ID
CODE LED
DESCRIPTION
High pressure alarm 1 from pres-
HPI
ID1
L5
sure switch
Low pressure alarm 1 from pres-
LPI
ID2
L6
sure switch
tP
ID3
L7
Pump thermal cutout alarm
Water tank low water level alarm /
LL
ID4
L8
No water fl ow
Protection alarm compressor 1
PII
ID6
L9
/ Phases monitor
Protection alarm compressor 3
PI3
ID7
L9
/ Phases monitor
1AC1
ID8
-
Circuit 1 alarm available
High pressure alarm 2 from pres-
HP2
ID6
L5
sure switch
Low pressure alarm 2 from pres-
LP2
ID7
L6
sure switch
Protection alarm compressor 2
PI2
ID11
L9
/ Phases monitor
Protection alarm compressor 4
PI4
ID12
L9
/ Phases monitor
1AC2
ID13
-
Circuit 2 alarm available
ICE310-360
4.6.2
Allarmi da ingressi analogici
AI
CODE
DESCRIPTION
RESET
Tank water outlet water high tempera-
HAI
ture alarm
M
Tank water outlet water low tempera-
B1
LAI
ture alarm
M
StI
Sensor open circuit or short circuit
Evaporator water outlet water high
M
HA2
temperature alarm
A
B2
Evporator water outlet water low tem-
LA2
perature alarm
M
St2
Sensor open circuit or short circuit
SP1
Transducer open or in short-circuit
M
P1
UnL1
UNLOAD Alarm
M
SP2
Transducer open or in short-circuit
P2
UnL2
M
UNLOAD Alarm

4.7 Automatic restart

M
In the event of a power failure, when power is restored the chiller will
assume theOn-Off statusheld at themoment the power was lost.