Programming the manual control

Activating the programming mode
• Press the "Scene 1" and "On" buttons simultaneously.
• Keep pressing this button combination until you hear a conf
firmation signal and "Scene 1", "Scene 2" and "Scene 3"
flash.
Note: If no further button is pressed following the start of
programming mode this is automatically terminated by the
manual programming device after approx. 30 seconds.
Locating luminaires
• Press the "Scene 1" button.
• The "Scene 1" button and the lamp symbol light up.
• The system now searches for luminaires nearby. When a
luminaire is located the lamp symbol and luminaire begin
to flash.
Adopting luminaires
Luminaires can be adopted into a group (room) or can be ig-
nored. To adopt a luminaire, proceed as follows:
• Press the "On" button on the manual control while the lumi-
naire flashes.
• The lamp symbol changes from flashing to continuous light-
ing.
• A confirmation tone is heard.
• The lamp symbol and a further luminaire start to flash.
• Repeat this process for all luminaires you wish to adopt.
Ignoring luminaires
• Press the "continue" button.
• The luminaire located next and the lamp symbol start to
flash.
Terminating luminaire search
• Press the "Scene 3" button.
26
Terminating programming
• After completing the luminaire search press the "Off" button.

Creating luminaire subgroups (creating zones)

If all luminaires have been adopted into the group (room),
proceed as follows:
• Activate programming mode
(press "Scene 1" and "On" buttons simultaneously
(see above, page 26).
• Confirm the "Scene 2" button.
• "Scene 2" and the lamp symbol flash.
• One luminaire flashes. Continue with:
a:
• Adopt luminaire with "Scene 1".
• A confirmation tone is heard.
b:
• Ignore luminaire with "continue".
• The next luminaire flashes.
c:
• Next subgroup with "Scene2".
• "Scene 2" and the lamp symbol flash.
• One luminaire flashes.
• Repeat this until all luminaires have been assigned.
• Terminate programming mode (see above, page 27).