Function
Oil burner pump
SUNTEC
J 7 C 1000
1
SUNTEC
SUNTEC
5
2
TECHNICAL DATA
General
Mounting
Flange mounting according to EN 225.
Model 1000
Connection threads
Conical
Cylindrical (according to ISO 228/1)
Inlet and return
1/4"NPTF
Nozzle outlet
1/8"NPTF
Pressure gauge port
1/8"NPSF
Vacuum gauge port
1/4"NPTF
Valve function
Pressure regulating and cut-off (except for 1002 models).
Strainer
Open area : 45 cm
²
Opening size : 170 μm
Shaft
Ø 11mm according to EN 225.
By-pass plug
Inserted in return port for 2 pipe system;
to be removed with a 3/16" Allen key for 1 pipe system.
Weight
4 kg
Hydraulic data
Nozzle pressure range
C : 10 - 21 bars
E : 10 - 30 bars
Delivery pressure setting 12 bars
Operating viscosity
2 - 75 mm²/s (cSt)
Oil temperature
0 - 90°C in the pump.
Inlet pressure
1,5 bars max.
Return pressure
1,5 bars max.
Suction height
0,45 bars max. vacuum to prevent air separation from oil.
Rated speed
3600 rpm max.
Torque (@ 45 rpm)
0,30 N.m
420010372500
1 - INLET
2 - RETURN
3 - BLEED AND PRESSURE
4
GAUGE PORT
4 - VACUUM GAUGE PORT
5 - PRESSURE ADJUSTMENT
6 - TO NOZZLE
The oil burner pump used is a self-priming
gear pump, which must be connected as
two-line pump via a bleed filter. There is an
intake filter and an oil pressure regulator
integrated in the pump. Pressure gauges
for pressure measurements and negative
6
pressure measurements must be
3
connected before the equipment is
commissioned.
NB: before starting the burner, check that
the return pipe is open. An eventual
obstraction could damage the pump
sealing device.
Capacity (L/h)
400
Models 1001/1002
300
G 1/2
G 1/4
200
G 1/8
G 1/2
100
0
5
Pump capacity
J 7
J 6
J 4
10
15
20
25
30
Pressure (bars)
Viscosity = 5 cSt - rated speed = 2850 rpm
Data shown take into account a wear margin.
Do not oversize the pump when selecting the
gear capacity.
PUMP
IDENTIFICATION
(Not all model combinations are available.
Consult your Suntec representative)
J : Pressure regulation
(see pump capacity curves)
and nozzle location
(seen from shaft end)
A : clockwise rotation/
right hand nozzle.
B : clockwise rotation/
left hand nozzle.
C : anti clockwise rotation/
left hand nozzle.
D : anti clockwise rotation/
right hand nozzle.
J
6
C
A
C 1 001
Flange mounting
000 : conical connection threads
cut-off function
001 : cylindrical connection threads
cut-off function
002 : cylindrical connection threads
by-pass nozzle, no cut-off function
Revision number
5 : for J4 and J6
4 : for J7
Installation
P : by-pass plug installed in return port
for two-pipe operation
Retour
35
à l'aspiration
Fioul en aspiration
Fioul sous pression
Retour du fioul
au réservoir ou à
l'aspiration
Aspiration
Joint
d'étanchéité
de l'arbre
Réglage
de la pression
Bouchon
de dérivation
monté
INSTALLATION
Retour
BITUBE
www.ecoflamburners.com
EN
Gear set capacity
Filter
Shaft rotation
Pressure range
C : 10-21 bars
E : 10-30 bars
5 P
Bouchon
de dérivation
retiré
Retour
INSTALLATION
obturé
MONOTUBE
Prise
vacuomètre
Engrenage
vers le
gicleur
Prise
manomètre
11