EN
Function
General safety functions
Description of functions
When the system is switched on for the
first time, after a power failure or safety
shutdown, after a lack of fuel or after the
system has been out of operation for 24
hours, the pre-ventilation period of 25
seconds begins.
During prepurge period:
- blower pressure is monitored.
- the combustion chamber is monitored for
flame signals.
At the end of the prepurge period:
- ignition is switched on.
- main and safety valve are opened.
- burner starts.
Monitoring
The flame is monitored by an
photoresistor. The burner switches to lock-
out if it doesn't survey the light of the
flame.
Safety functions
- If no flame is produced when the burner
is started, the burner will be switched off at
the end of the safety period, lasting no
more than 5 seconds, and the oil valve will
close.
- If the flame goes out during operation,
the oil supply is interrupted within one
second. A restart takes place. Once the
105
8
www.ecoflamburners.com
burner starts, operation is continued.
Otherwise, a safety lock-out occours.
- If there is a lack of air during
preventilation or operation, a safety lock-
out occours.
- If there is a lack of oil, the burner does
not begin operation or switches off.
In the event of controller shutdown
- Controller thermostat interrupts heat
request.
- Oil solenoid valves close.
- Flame goes out.
- Burner motor switches off.
- Burner is ready for operation.
101
HS
M
M1
102
106
104
Y1
103
T1
118
Y3
Y2
M1
Burner motor
HS
Hydraulic system
T1
Trasformatore
Y1
Solenoid valve
Y2
Solenoid valve
Y3
Solenoid valve
101
Blower / Fan
102
Oil pump
103
Air damper
104
Oil pressure regulator
105
Hoses
106
Filter
118
Nozzle