3.5 — Turning the Generator Off When Operating Under Load
NOTE: Important! To turn the generator off during prolonged utility outages to perform maintenance or conserve
fuel, follow these simple, but important steps:
To turn the generator OFF (while running in AUTO and online):
1. Turn OFF (or OPEN) the main Utility disconnect.
2. Turn OFF (or OPEN) the Main Line Circuit Breaker (MLCB) on the generator. and allow the generator to run for 1
minute to cool down.
3. Turn the generator OFF. If the generator is to remain off for more than an hour, remove the 7.5 Amp fuse from the
control panel to avoid running down the starting battery, if utility is not present.
To turn the generator back ON:
1. Put the generator back into AUTO and allow to start and warm-up for a few minutes.
2. Turn ON (or CLOSE) the MLCB on the generator.
The system will now be operating in its automatic mode. The main utility disconnect can be turned ON (or CLOSED), but to shut the unit off, this
complete process must be repeated.
3.6 — Manual Transfer Operation
DO NOT attempt to activate the transfer switch manually until all power voltage supplies to the switch have been
completely turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possi-
bly fatal electrical shock.
Prior to automatic operation, manually exercise the transfer switch to verify that there is no interference with proper operation of the mechanism.
Manual operation of the transfer switch is required if electronic operation should fail.
3.6.1— Transfer to Generator Power Source - 100/200 Amp
Figure 3-4: Manual Transfer Switch Operation
Automatic Standby Generator Owner's Manual
1.
Press the Control Panel OFF button.
2.
Set the Main Circuit Breaker (Generator
Disconnect) to its OFF (OPEN) position.
3.
Turn off the utility power supply to the transfer
switch using the means provided (such as a utility
main line circuit breaker).
4.
Use the manual transfer handle inside the transfer
switch to move the main contacts to their STANDBY
positions (loads connected to the standby power
source).
5.
To crank and start the engine, press the Control
Panel MANUAL button.
6.
Allow the engine to stabilize and warm up for a few
minutes.
7.
Set the Main Circuit Breaker (Generator
Disconnect) to its ON (CLOSED) position. The
standby power source now powers the loads.
15