2. Connect the connector specified in the main printed circuit.
3. Connect the system.
If you need to disconnect these detectors for a period in excess of 30 min, the reverse of the above process will apply,
and then you have to put the connector back with the 9V battery.

INSTALLATION OF INTERFACES 8 INPUTS 4-20mA

The interfaces 8 inputs 4-20mA allow to connect and address to EUROSONDELCO Control Unit any detector with 4-20mA
standard format.
The following configurations can be installed per module line:
• 1 Interface for 8 detectors 4-20mA
• 1 Interface for 8 detectors 4-20mA
• 16 Eurodetectors / EXP Detectors
Selecting the group number and detector number connected to each interface:
The detectors connected to the interfaces are numbered automatically according to the input number they are connected
to.
• When selecting JP1 in ON position for the first Interface. This indicates that the connected detectors - from
1 to 8 – belong to group 1, in modern interfaces SW1-3 in ON.
• When selecting JP1 in OFF position for the second Interface. This indicates that the connected detectors -
from 9 to 16 – belong to group 2, in modern interfaces SW1-3 in OFF.
Bottom of scale for the different detectors and gas type are:
Carbon Monoxide CO
Explosives EXP
Oxygen O
Nitrogen Dioxide NO
Chlorine CI
Other toxic gases

2. PRINTER CONFIGURATION -optional-

+
+
2
2
and Ammonia NH
2
3
Baud Rate
Data Bit
Parity
Character
CR BB
CR AFB
CR
8 Eurodetectors (toxic g.) / EXP Detectors
1 Interface for 8 detectors 4-20mA
From 0 to 400 ppm
From 0 to 100% L.E.L.
From 0 to 25%
From 0 to 20 ppm
From 0 to 100 ppm
From 0 to 200 ppm
2.400 bps
8
None
U.S.A.
LF
LF
LF
31
X-maneuro-INS-v04