7. CO DETECTION, ITALIAN STANDARD. Default configuration
If you do not need to change any of the parameters described, it will not be necessary to enter the SYSTEM
PROGRAMMING menu.
If you need to change any of the parameters, go directly to that parameter by pressing FORWARD.
1, 2 or 4 VENTILATION GROUPS
Ventilation:
Alarm:
Number of groups:
Cyclical ventilation:
Cyclical ventilation activation time:
Overhauls Interval:
Engineer code:
PROGRAMMING THE SYSTEM
With the Module line in OFF position:
1. Press PROGRAMMING.
"Insert Code" is displayed. Insert the Engineer Code -default setting: 66666. Press ENTER 5 times-.
NUMBER OF GROUPS
Number of Groups is displayed -default setting: 1-
2. Press FORWARD to select the number of groups: 1, 2 or 4 groups.
3. Press ENTER to memorise.
SETTING THE GROUPS
4. Press PROGRAMMING to set the groups.
"Group 1" is displayed.
5. Press FORWARD to select the other groups.
6. Press PROGRAMMING.
Type of gas is displayed -default setting: CO-.
7. Press PROGRAMMING to select other gases.
8. Press FORWARD to select the type of gas -CO, H
9. Press ENTER to memorise.
Alarm level Group 1 is displayed -default setting: 200 ppm-.
10. Press PROGRAMMING to change to other levels.
11. Press FORWARD to select the alarm level.
ON: If 2 detectors are at 50 ppm -1 minute input retard-
ON: 1 100-ppm detector -with 1 minute input retard-
OFF: whenever one of the ON conditions is not met -2 minutes
output retard-
ON 200 ppm -3 minutes input retard-
1
Each "0" hours
5 minutes
Each "0" months
66666 -5 times ENTER -