Group Number; Groups Configuration: Type Of Gas And Levels - Duran Electronica EUROSONDELCO Manual De Instalación

Deteccion de gases toxicos y explosivos
Ocultar thumbs Ver también para EUROSONDELCO:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

GROUP NUMBER

The system has been programmed 1 group by default, if you need to program more groups:
1. Press PROGRAMMING.
1, 2 or 4 will be displayed.
2. Press FORWARD to select a different group.
3. Press ENTER to memorise.

GROUPS CONFIGURATION: Type of gas and levels

To configure the groups:
1. Press PROGRAMMING.
"Group 1" will be displayed.
2. Press FORWARD until you select the desired group (if you have selected more than one).
3. Press PROGRAMMING to enter the selected group.
The type of gas will be displayed.
4. Press PROGRAMMING if you to change this gas.
The different gases will be displayed: "CO, H
5. Press FORWARD to select the wanted one.
6. Press ENTER to memorise.
The alarm level of the group 1 "100 ppm" will be displayed.
7. Press PROGRAMMING if you want to change it.
The different alarm levels will be displayed:
Carbon Monoxide CO
Explosives EXP
Oxygen O
2
Nitrogen Dioxide NO
Chlorine CI
2
Other toxic gases
8. Press FORWARD to chose the alarm level.
9. Press ENTER to memorise.
The ventilation level "50ppm" will be displayed.
10. Press PROGRAMMING if you want to change it.
11. Press FORWARD and select the wanted one.
12. Press ENTER to memorise.
The ventilation input retard "1 min" will be displayed. This menu allows to program a retard from the
moment the ventilation condition is detected until the ventilation acts.
13. Press PROGRAMMING if you want to change it.
14. Press FORWARD and select the wanted one -from 0 to 4 min-.
15. Press ENTER to memorise.
The ventilation output retard "2 min" will be displayed. This menu allows to program a retard from the
moment the no-ventilation condition is detected until it is disconnected.
16. Press PROGRAMMING if you want to change it.
17. Press FORWARD and select the wanted one -from 0 to 4 min-.
18. Press ENTER to memorise.
If you have programmed more than 1 detection group then repeat same steps for the rest of groups.
From 20 to 390 ppm
From 10 to 90% L.E.L.
From 2 to 24%
From 1 to 19 ppm
2
and Ammonia NH
From 1 to 99 ppm
3
From 1 to 195 ppm
S, SO
, NO, NO
, Cl
, HCl, O
2
2
2
2
in steps of 10 ppm
in steps of 5 %
in steps of 1 %
in steps of 1 ppm
in steps of 1 ppm
in steps of 1 ppm
, NH
EXP".
2
3,
X-maneuro-INS-v04
33

Publicidad

Tabla de contenido
loading

Tabla de contenido