7. Press FORWARD to change the group.
8. Press PROGRAMMING to change the parameters.
Type of gas is displayed -default setting: CO-.
9. Press PROGRAMMING to change the type of gas.
10. Press FORWARD to select the type of gas -CO, H
11. Press ENTER to memorise.
Group 1 alarm level is displayed -default setting: 200 ppm-.
12. Press PROGRAMMING to change the alarm level.
13. Press FORWARD to select the alarm level.
CO
NO
Other toxic gases
O
2
EXP explosive gases From 10% to 90%
14. Press ENTER to memorise.
Ventilation level 1st speed is displayed -default setting: 50 ppm-.
15. Press PROGRAMMING to change the ventilation level.
16. Press FORWARD to select the level.
17. Press ENTER to memorise.
Ventilation level 2nd speed is displayed -default setting: 100 ppm-.
18. Press PROGRAMMING to change.
19. Press FORWARD to select the level.
20. Press ENTER to memorise.
Ventilation input retard is displayed -default setting: 1 minute-.
This menu allows a retard to be programmed from the moment the ventilation condition is detected until
ventilation begins.
23. Press PROGRAMMING to change the retard.
24. Press FORWARD to select the retard -from 0 to 4 minutes-.
25. Press ENTER to memorise.
Ventilation output retard is displayed -default setting: 0 minutes-.
This menu allows a retard to be programmed from the moment the non-ventilation condition is detected
until it is disconnected.
26. Press PROGRAMMING to change the retard.
27. Press FORWARD to select the retard -from 0 to 4 minutes-.
28. Press ENTER to memorise.
2
From 20 to 390 ppm
From 2 to 20 ppm
2
From 20 to 190 ppm
From 2% to 24%
S, SO
, NO, NO
, Cl
, HCl, O
2
2
2
, NH
EXP-.