8. CO DETECTION, FRENCH STANDARD. Default configuration
If you do not need to change any of the parameters described, it will not be necessary to enter the SYSTEM
PROGRAMMING menu.
If you need to change any of the parameters, go directly to that parameter by pressing FORWARD.
1 or 2 INDEPENDENT VENTILATION GROUPS
Ventilation:
Ventilation:
Alarm:
Number of groups:
Cyclical ventilation:
Cyclical ventilation activation
time:
Overhauls Interval:
Engineer code:
Alarm average:
PROGRAMMING THE SYSTEM
With the Module line in OFF position:
1. Press PROGRAMMING.
"Insert Code" is displayed. Insert the Engineer Code -default setting: 66666. Press ENTER 5 times-.
Alarm type is displayed
MODES:
• 20-minute averages. One measurement every 5 minutes, if equal to or above 100 ppm the event is
memorised.
• 8-hour averages. One measurement every 20 minutes, if equal to or above 50 ppm the event is
memorised.
2. Press FORWARD to select the type of alarm.
3. Press ENTER to memorise.
NUMBER OF GROUPS
Number of groups is displayed: 1 or 2 groups -default setting: 1-.
4. Press FORWARD to select the number of groups.
5. Press ENTER to memorise.
SETTING THE GROUPS
6. Press PROGRAMMING to change the group.
"Group 1" is displayed.
46
© 2012 DURAN ELECTRONICA S.L.
All rights reserved · www.duranelectronica.com
1st Speed
ON: 50 ppm -1 minute input retard-
OFF: < 50 ppm -instant-
2nd Speed
ON: 100 ppm -1 minute input retard-
OFF: < 100 ppm -instant-
ON 200 ppm -instant-
1
Each "0" hours
5 minutes
Each "0" months
66666 -5 times ENTER -
20 minutes