2 In case of collective installation and continuous installation
• When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and passageways between groups of units as shown in the
figures.
* Leave both sides of each group of units open.
• As with single installation, if the wall height exceeds the height limit, widen the space in the front and the back of a given group of units by the amount that exceeds
the limit (labeled <h> in the figure).
• If there is a wall at both the front and the rear of the unit, install up to six units (three units : P120, 144) consecutively in the side direction and provide a space of 1000
mm or more as inlet space/passage space for each six units (three units : P120, 144).
[Fig. 6.0.2]
(1) Side-by-side installation
<The space on both sides of a given group of units is minimum.>
*
30 [1-3/16]
h
Unit height
(2) Face-to-face installation
<There are walls in the front and the back of a given group of units.>
*
h
Unit height
450 [17-23/32] + h
(3) Combination of face-to-face and side-by-side installations
<There are walls in the front and the back of a given group of units.>
*
h
500
[19-11/16]
h
500 [19-11/16]
300 [11-13/16] + h
*
450 [17-23/32] + h
h
500 [19-11/16]
100 [3-15/16] + h
450 [17-23/32]
*
450 [17-23/32]
h
500
[19-11/16]
300
[11-13/16] + h
900 [35-7/16]
*
300 [11-13/16] + h
<The space on both sides of a given group of units is minimum.>
*
100
[3-15/16]
h
Unit height
<There is a wall on one side.>
h
Unit height
15 [19/32] + h
<There is a wall on one side and either the front or the back of a given group of unit.>
1000
[39-3/8] + h
*
h
500 [19-11/16]
100 [3-15/16] + h
*
450 [17-23/32] + h
450 [17-23/32]
450 [17-23/32]
h
Unit height
300
[11-13/16] + h
*
900 [35-7/16]
(Unit : mm [in.])
h
500
[19-11/16]
7