Unit description
2.8. Specifications tables
DC inputs
Recommended power range of PV array
Maximum input voltage
(2)
Voltage range MPP1
(3)
Voltage range MPP2
(3)
Operating voltage range
Minimum voltage for Pnom
Maximum short circuit current (input 1 / input 2)
Maximum inverter backfeed current to the PV array.
MPPT
Number of strings (input 1 / input 2)
Maximum input current (input 1 / input 2)
Maximum input current per string
(4)
AC output
Rated power
Maximum continuous power
Max. temperature for nominal power
Maximum current
Maximum transient current
Maximum output fault current
Maximum output overcurrent protection
Rated voltage
Voltage range
Nominal frequency
Cosine of Phi
Adjustable cosine of phi
THD
Performance
Maximum efficiency
CEC
General data
Cooling system
Air flow
Weight
Measurements (height x width x depth)
Standby current
(6)
Night consumption
Operating temperature
Relative humidity (without condensation)
Maximum altitude of the installation
Protection class
DC AFCI
Markings
EMC and safety regulations
Grid connection regulations
Depending on the type of installation and the geographic location.
(1)
low temperatures.
The output power will be determined by the voltage and current configuration selected at each input.
(3)
of the first three strings can not surpass 30 A, or the sum of the three last strings.
Consumption from the PV array.
ABO2012IQM01_ - Installation and Operation Manual
(1)
(5)
27.8 x 28.9 x 10.55 in (730 x 700 x
-13 ºF ~ 149 ºF (-25 ºC ~ 65 ºC)
UL1741, FCC Part 15, IEEE C37.90.1,
IEC 62116, UL1741, IEEE1547,
IEEE1547.1, NEC CODE
Never exceed this value. Consider the voltage increase of the panels 'Voc' at
(2)
40TL U M480
24.7 ~ 32.2 kWp
1000 V
200 ~ 820 V
200 ~ 820 V
200 ~ 1000 V
520 V
44 / 44 A
0 A rms
2
1 / 1
40 / 40 A
12 A
40 kW
40 kW
113 ºF (45 ºC)
48 A
48 A
52.8 A @ 60 ms
52.8 A rms
480 V
423 ~ 528 V
60 Hz
1
Yes. Smax = 40 kVA
< 3 %
98.5 %
98 %
Forced ventilation
3.92 ft
/s (400 m
/h)
3
3
137.79 lb (62.5 Kg)
250 mm)
< 10 W
< 1 W
0 ~ 95 %
13,123 ft (4000 m)
NEMA 4
Yes
CE, ETL CE, ETL
IEEE C37.90.2
(5)
For each ºF of increase, the output power is reduced by 1.8 %.
Ingeteam
The sum of the currents
(4)
(6)
13
EN
ES