Preparation for installing the unit
•
Keep the following distances free of obstacles.
* If the unit connects via a connections box supplied by Ingeteam, this may be placed in the lower part.
5.2. Environmental conditions
Environmental operating conditions indicated in section "2.8. Specifications tables" must be taken into account
when choosing the location of the unit.
The surrounding atmosphere must be clean and at temperatures above 104 ºF (40 ºC), the relative humidity must
be between 4% and 50%. Higher percentages of relative humidity up to 95% are tolerated at temperatures below
86 ºF (30 ºC).
Take into account that moderate condensation may occasionally occur as a consequence of temperature variations.
For this reason, apart from the unit's own protection, it is necessary to monitor these units once they have been
started up on sites where the conditions described above are not expected to be present.
In the event of condensation, never apply voltage to the unit.
5.3. Supporting Surface and Fastening
These inverters must be installed in accordance with the specifications in the following figure. The permitted
positive inclination is between the range of 15 to 90º. The installation with negative inclination (example on the
right) is not permitted.
Reserve a solid wall to which to attach the unit. It must be possible to drill the wall and fit suitable wall anchors
and self-tapping screws to support the unit's weight.
ABO2012IQM01_ - Installation and Operation Manual