Electric Wiring Work; Electrical Characteristics - Daikin FXFQ07TVJU Manual De Instalación

Ocultar thumbs Ver también para FXFQ07TVJU:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4. When the power supply is turned on, the drain pump
should operate. Drainage can be checked at the
transparent part of the drain socket.
(The drain pump will automatically stop after 10
minutes.)
After checking the drainage of water, refer to Fig. 20
and attach the sealing material (14) to perform the
thermal insulation of the drain socket.
• Do not connect the drain piping directly to the
sewage that gives off ammonia odor.
The ammonia in the sewage may go through the
drain piping and corrode the heat exchanger of
the indoor unit.
• Do not apply external force to the float switch or it
could cause malfunction.
5. Turn off the power supply after checking drainage,
and remove the power supply wiring.
6. Attach the control box lid as before.
• Do not touch the electronic parts other than the
terminal block (X2M).
(3) Sweating may occur and result in water leakage.
Therefore, make sure to insulate the indoor drain pip-
ing and socket locations.
After drainage is checked, put the attached sealing
material (14) referring to Fig. 20, and insulate the drain
hose (1) and the metal clamp (2) with the attached seal-
ing material (Large) (10) referring to Fig. 22.
Sealing material - Large
(10) (accessory)
Be sure to lay the
sealing material
(10) on (14).
Sealing material (14)
(accessory)
Sealing material (Large) (10)
Drain hose (1)
(accessory)
(accessory)
Start wrapping from where the
metal clamp (2) is tightened.
Metal clamp (2)
(accessory)
Wrap the sealing material (Large) (10)
so that the metal clamp (2) end side
may be doubled.
Fig. 22
11
Do not have
the clearance.

7. ELECTRIC WIRING WORK

7-1 GENERAL INSTRUCTIONS
• Make sure that all electric wiring work is carried out by
qualified personnel according to the applicable legislation
and this installation manual, using a separate dedicated
circuit.
Insufficient capacity of the power supply circuit or improper
electrical construction may lead to electric shocks or a fire.
• Make sure to install a ground fault circuit interrupter.
Failure to do so may cause electrical shocks and a fire.
• Do not turn on the power supply (branch switch, branch
overcurrent circuit breaker) until all the works are finished.
• Multiple number of indoor units are connected to one out-
door unit. Name each indoor unit as A-unit, B-unit ..... and
the like. When these indoor units are wired to the outdoor
unit and the BS unit, always wiring the indoor unit to the ter-
minal indicated with the same symbol on the terminal block.
If the wiring and the piping are connected to the different
indoor units and operated, it will result in malfunction.
• Make sure to ground the air conditioner.
Grounding resistance should be according to applicable
legislation.
• Do not connect the ground wiring to gas or water pipings,
lightning conductor or telephone ground wiring.
• Gas piping .................Ignition or explosion may occur if
the gas leaks.
• Water piping ..............Hard vinyl tubes are not effective
ground.
• Lightning conductor or telephone ground wiring ..............
Electric potential may rise abnormally if struck by a light-
ning bolt.
• For electric wiring work, refer to also the WIRING DIA-
GRAM attached to the control box lid.
• Carry out wiring between the outdoor units, indoor units
and the remote controllers according to the wiring diagram.
• Carry out installation and wiring of the remote controller
according to the installation manual attached to the remote
controller.
• Do not touch the Printed Circuit Board assembly. It may
cause malfunction.

7-2 ELECTRICAL CHARACTERISTICS

Units
Voltage
Model
Hz
Volts
FXFQ07TVJU
FXFQ09TVJU
FXFQ12TVJU
FXFQ15TVJU
208/
Max. 253
FXFQ18TVJU
60
230
Min. 198
FXFQ24TVJU
FXFQ30TVJU
FXFQ36TVJU
FXFQ48TVJU
MCA: Min. Circuit Amps (A)
kW: Fan Motor Rated Output (kW) FLA: Full Load Amps (A)
Power
Fan motor
supply
MCA MFA
kW
FLA
range
0.3
15
0.048
0.2
0.3
15
0.048
0.2
0.3
15
0.048
0.2
0.4
15
0.048
0.3
0.6
15
0.048
0.5
0.7
15
0.048
0.5
1.3
15
0.106
1.0
1.5
15
0.106
1.2
1.8
15
0.106
1.4
MFA: Max. Fuse Amps (A)
3P161684-7N
English

Publicidad

Tabla de contenido
loading

Tabla de contenido