4 Product Overview
Symbol
Explanation
Inverter
Together with the green LED, this symbol indicates the operating state of the in-
verter.
Data transmission
Together with the blue LED, this symbol indicates the status of the network con-
nection.
Equipment Grounding Terminal
This symbol indicates the position for the connection of an equipment ground-
ing conductor.
The product is has no galvanic isolation.
UL 1741 and CSA C22.2 No. 107.1 are the standards applied by Under-
writers Laboratories to the product to certify that it meets the requirements of
the National Electrical Code
IEEE 1547.
4.3

Interfaces and Functions

The inverter can be equipped or retrofitted with the following interfaces and functions:
User interface for monitoring and configuration
The product is equipped as standard with an integrated webserver, which provides a user interface
for configuring and monitoring the product. The product user interface can be called up via the web
browser if there is an existing connection to an end device (e.g. computer, tablet PC or
smartphone).
Smart Inverter Screen
The Smart Inverter Screen enables you to view the status display and to display the nominal energy
throughput and state of charge of the battery on the user interface login page. You therefore have
an overview of the most important inverter and battery data without having to log into the user
interface.
The Smart Inverter Screen is deactivated by default. The Smart Inverter Screen can be activated via
the user interface once the inverter has been commissioned.
SMA Speedwire
The product is equipped with SMA Speedwire as standard. SMA Speedwire is a type of
communication based on the Ethernet standard. SMA Speedwire is designed for a data transfer
rate of 100 Mbps and enables optimum communication between Speedwire devices within
systems.
Class 1 wiring methods are to be used for field wiring connection to the terminals of the
communication interface.
16
SBSxx-US-10-IA-xx-12
®
, the Canadian Electrical Code