Site Selection; Cord-And Plug Installation - Siemens VersiCharge Manual De Instalación Y Funcionamiento

Ocultar thumbs Ver también para VersiCharge:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

• Ground Fault Circuit Interrupter (GFCI) recommendation
To provide additional protection, Siemens recommends the use
of GFCI circuit breakers. Though this is not required by code,
this will provide an additional level of protection for users and
their property.
• Siemens Part numbers: QF240 (plug-in type), BF240 (bolt-
on type).
• The VersiCharge must be wired on a dedicated circuit, with no other
loads wired on that circuit.

3.2 Site Selection

• Accessibility
• Select a mounting site that is close to the charging connection of
the vehicle.
• Allow 21.5 inches minimum clearance for the connector between
the wall and anything in the area.
• The VersiCharge will mount on the surface of the wall, and a
location for installation should be chosen where there is
sufficient space to park a vehicle, walk past the device, open
nearby doors, etc., without obstruction.
DANGER
parts that should not be exposed to flammable vapors. This equipment
should be installed at least 18 inches above floor or ground level. Use
extreme caution and follow instructions carefully.
3.3 Cord-and-plug Installation
© 2012 Siemens Industry, Inc.
Explosion hazard. This equipment has arcing or sparking
- 13 -
Document Number: 813540

Publicidad

Tabla de contenido
loading

Tabla de contenido