The unit arrives factory-configured for either bottom fed cord-and-plug
installation or fed from behind cord-and-plug installation. Do not
relocate the cord-and-plug assembly. Once removed, it cannot be re-
installed.
WARNING! The cord-and-plug assembly cannot be relocated from
bottom-fed to fed-from-behind or vise versa. This change will violate
UL listings and void the device warranty.
WARNING! The cord-and-plug assembly can only be used for indoor
installation. Due to the risk of moisture, cord-and-plug installations are
not listed for outdoor use. Installing outdoors with the cord-and-plug
assembly will violate listings and void the device warranty.
Bottom-fed, Cord-and-Plug Installation
•
• Mounting
• Locate a stud within the wall to attach the mounting bracket and
receptacle. For concrete or masonry walls, install appropriate
anchors.
• Verify that the stud or anchor and surrounding materials can
• Verify local code with respect to installation height:
• Receptacle will be located below VersiCharge Mounting
• Installation height is regulated by the NEC®, however this
© 2012 Siemens Industry, Inc.
handle the 20+ lbs load of the VersiCharge.
Bracket. Verify receptacle location complies with local code
requirements.
can vary based on local jurisdiction.