Installation; Installation Requirements - Munters EM Serie Manual De Uso Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

not intended to handle materials which release explosive
dust. Emission into the atmosphere of harmful particles or
gases must be contained within the limits established by
current regulations.
The fan has been designed and built in such a
way that it CANNOT operate in a classified
Ex
area, according to directive 1999/92/EC.

5. Installation

After fan has been delivered but before fitting and
installation, check condition of the consignment: in the
event of discrepancy or damage to the machine, the
manufacturer or carrier must be informed immediately.
Fitting and installation of the fan must be
!
performed by specialized personnel, in order
to prevent damage to the equipment or
hazards to people as a result of faulty fitting.
Fitting the fan must be carried out according to the
following stages:
• positioning and anchoring the fan;
• connection to the mains electricity supply;
• operational testing and putting into operation.
5.1
CHOICE
OF

INSTALLATION REquIREMENTS

The user is responsible for preparing an area suitable
for installation of the equipment and complying with
the requirements laid down by European directives
and national law governing safety at places of work.
Environmental conditions for operating the equipment
are as follows:
Ambient temperature
during operation
Ambient humidity
during operation
Tab. 3
For operation of fan installation, a manoeuvring area
must be made available that is suitable for the fan
dimensions and the chosen lifting equipment: electrical
points must be provided in the installation area for fan
connection to the mains electricity supply.
SITE
AND
CHECkING
-25°C/+50°C
<90%
© Munters AB, 2013
The fans must be installed at a height of not
!
less than 2.7 m from the ground. If they are
installed at a lower height, the fans must be
fitted with the optional safety mesh supplied by the
manufacturer, to protect the internal rotor. Failure to
install the safety mesh releases manufacturer from
all liability and shall be considered an improper use
of the machine.
Irrespective of the place of installation, suitable indelible
warning signs are attached to the fan, warning of danger
and giving instructions to remain at a safe distance not to
place hands inside the shutter and not to run in proximity
of the fan. The warning signs are yellow, self-adhesive
and indelible. They are fitted to the front and rear of the
fan, and marked with the numbers A-1997 and B-1997
(see fig.1). The area adjacent to the fan in the premises
from which air is being extracted must be kept clear to
allow the air to exit freely. It is also prohibited for anyone
to remain in this area, because of the presence of organic
gases and dust which may be present in the airflow.
The fans must be installed to carry out
!
extraction or an internal circulation of the air
present in the area, and must not operate
under pressure. It is also permissible to install the fan in
a horizontal position.
5.2 INSTALLING SERIES EM FANS
If the fan is fixed directly to a metal structure, M8 bolts
type 8.8 must be used, screwing them into the threaded
inserts provided for the purpose on the bodywork (two
per side).
If the fan is installed in a masonry structure, an iron outer
frame must be constructed (not supplied with the fan),
with a 60 mm L-shaped profile at least 5 mm thick, with
suitably-sized clamps. When the outer frame is properly
built-in, i.e. perfectly level and upright, insert the fan,
screwing four M8 bolts type 8.8 (not supplied with the
fan) into the threaded inserts provided on the sides of the
bodywork, two per side.
5.3 INSTALLING SERIES EMS FANS
For installing type EMS fans in metal or masonry
structures, the procedures described on the previous
page for model EM fans also apply. If installed for
7