Software Dongles For Ec Sensors; Deactivating Dongles; Sensor Settings Pointgard 2100 Ec; Sensor Test - Dräger PointGard 2000 Serie Instrucciones De Uso

Ocultar thumbs Ver también para PointGard 2000 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 101
On
The instrument rejects any sensor whose
part number does not match the part num-
ber of the previously installed sensor.
Off
The instrument accepts any suitable sensor,
uploading the default settings of this sensor.
However, this overwrites any customized
settings with the default settings of the new
sensor.

14.6 Software dongles for EC sensors

14.6.1 Deactivating dongles

PointGard 2100 EC-specific:
This function deactivates a SW dongle to safely remove the
dongle or if the dongle is faulty.
A dongle can only be reactivated by cycling the power to the
instrument.
1. Select Settings > Instrument > SW dongle and the
dongle to be deactivated and confirm.
2. Select Deactivation func. The selected dongle is
deactivated.

14.7 Sensor settings PointGard 2100 EC

14.7.1 Sensor test

This function is only active if the sensor test or diagnostics
dongle is installed. If the sensor does not pass the self-test, a
warning or fault message is issued.
Setting periodic sensor test
This function periodically initiates the sensor self-test. The
instrument routinely checks the sensor for proper function.
1. Select Settings > Sensor > Set sensor test and confirm.
2. Select Enable or Disable and confirm.
Starting sensor test manually
This function starts a singular sensor test.
1. Select Settings > Sensor > Sensor test and confirm.
2. Select Start sensor test and confirm.
3. Select Confirm
✓ The test result is displayed.

14.7.2 Gas settings

Setting gas settings
This function sets the gas type, measuring range and units of
measurement. Only certain sensors support these settings.
1. Select Settings > Sensor > Gas setting and confirm.
 The current measured gas is displayed.
2. Select a measured gas from the list and confirm.
 The current unit of measurement is displayed.
3. Select the unit of measurement from the list and confirm.
 The current full scale deflection is displayed.
Instructions for use
|
Dräger PointGard 2000 Series
Sensor settings PointGard 2xx0
4. For certain EC sensors only: Set the full scale deflection
and confirm.
 The new full scale deflection is displayed.
5. Select Next and confirm.
 An overview of the new gas settings is displayed.
6. After review, select Back to menu or Confirm.
Back to menu
Confirm

14.8 Sensor settings PointGard 2200 CAT

14.8.1 Sensor type

This function defines the sensor type installed.
1. Select Settings > Sensor > Sensor type and confirm.
2. Select the sensor type and confirm.
14.8.2 Gas settings
This function sets the unit of measurement.
For LC sensors, this function also sets the full scale
deflection.
1. Select Settings > Sensor > Gas setting and confirm.
2. Select the unit of measurement from the list and confirm.
 For DQ sensors and DSIR:
An overview of the new gas settings is displayed.
Continue with step 4.
 For LC sensors:
The current full scale deflection is displayed. Continue
with step 3.
3. Set the full scale deflection and confirm (only for LC
sensors).
 An overview of the new gas settings is displayed.
4. After review, select Back to menu or Confirm.
Back to menu
Confirm

14.8.3 Setting DQ sensor latching

This function is only available without relays installed. This
function configures whether the DQ sensor must be
acknowledged after a measurement at higher concentration
than 100%LEL.
This setting does not apply for LC sensors.
1. Select Settings > Sensor > DQ Sensor latch. and
confirm.
 The current setting is displayed.
|
Select Back to menu for leav-
ing the function without
changes and confirm with
[OK].
Select Confirm to accept the
settings and confirm with
[OK].
Select Back to menu for leav-
ing the function without
changes and confirm with
[OK].
Select Confirm to accept the
settings and confirm with
[OK].