Main Components; Installation; Boiler Room - Sime RMG 70 Mk.II Manual De Instrucciones

Ocultar thumbs Ver también para RMG 70 Mk.II:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1.4

MAIN COMPONENTS

2

INSTALLATION

The boiler must be installed in a fixed loca-
tion and only by specialized and qualified
firms in compliance with all instructions
contained in this manual.
Furthermore, the installation must be in
accordance with current standards and
regulations.
2. 1

BOILER ROOM

The "RMG Mk.II" boilers with a rating of
more than 35 kW must be equipped with a
technical room whose dimensions and
requirements correspond to the current
safety standards.
The minimum height of the boiler room
must comply with what is indicated in fig. 3
in relation to the overall thermal capacity.
The minimum distance between the walls of
the room and the external points of the boi-
ler (right, left side, rear) must not be less
than 0.60 m.
It is possible to place a number of appara-
tus next to each other, on condition that all
the safety and control devices can be
easily reached. In addition, to circulate air
in the room, air vents must be made on
the outside walls for which the surface
area must never be less than 3,000 cm
and 5,000 cm
2
for gas with a density
greater than 0.8.
KEY
1
Gas valve with coil assembly
2
1/2" bulb holder
3
Safety stat
4
Lock out reset button
5
Main switch
6
Regulation sta with double contact
7
Thermometer
8
Smoke stat
("70 - 80 - 90 100" models)
9
1/8" pressure test point
("110" models)
10
1/8" pressure test point
11
Burner manifold
2. 1 . 1
Handling
Once the boiler is in its place of installation
and the packaging has been removed, pro-
ceed as follows if it must be moved (fig. 3/a):
2
– remove the casing cover;
– attach the lifting brackets (located on the
rear of the boiler) and fasten it in place
H in relation to the overall
thermal capacity:
– not greater than 116 kW: 2.00 m
– greater than 116 kW and less
than 350 kW: 2.30 m
– greater than 350 kW and less
580 kW: 2.60 m
– greater than 580 kW: 2.90 m
IT
ES
PT
GB
Fig. 2
Fig. 3
49