Charging errors
12 V or 24 V operating indicator lit, fault indicator flashing, charge level indicator
1/2/3/4 flashing
Cause:
Remedy:
Cause:
Remedy:
Characteristic
Safety
Characteristic
No. Characteristic
1
IUo U
2
IUo U
... Factory setting
Timeout in the corresponding charging phase, or battery capacity too high
Select correct characteristic type according to the enclosed characteristic
data sheet and charge again
Battery faulty (cell short circuit, heavy sulphation)
Check battery and replace if necessary
WARNING! Operating the equipment incorrectly can cause serious injury and
damage. Follow the battery manufacturer's instructions. The battery must not
be connected to the charger when setting parameters.
Code
Battery
Standard wet charging
Standard gel charging
I
1
U
1
Capacity
[Ah]
-
-
IUo U
U
I
Main charging current
2
1
U
End-of-charging voltage
1
U
Conservation charging voltage
2
13
I
U
I
U
1[A]
1 [V/Cell]
2[A]
2 [V/Cell]
35
2.40
-
2.25
35
2.35
-
2.25