Installation
Before installation, check strength and horizontality of the base so that abnormal sound does not generate.
According to the dimensions and clearances, fix the base firmly with the anchor bolts (Anchor bolt, nut: M10 x 2
pairs).
Required tools for installation
- Philips screw driver
- Cutter drill (65 mm)
- Spanner
- Pipe cutter
- Cutter
- Reamer
- Gas leak detector
- Meter
- Thermometer
Filed supplied material
Refrigerant pipes; Pipe insulating material (polyethylene foam, 6 mm thick), Putty, PVC tapes.
Knockout procedure
The indoor/outdoor connecting pipes can be connected
to 4 directions (See fig. 4)
Take off the knockout part of the pipe cover in which
pipes or wires pass through the base plate.
Do not remove the pipe cover from the cabinet so that
the knockout hole can be easily punched.
How to remove the front panel
1. Remove screws of the front panel (See fig. 6).
Drain hose and base pan knockouts
See fig. 7.
In case of draining through the drain hose, attach the
drain nipple (A) and use the drain hose (Inner diam.:
16mm) sold on the market. When there is a possibility of
- Volt-ohm-milliammeter
- Electro circuit tester
- Hexagonal wrench
- Flare tool
- Pipe bender
- Water level
- Metal saw
- Hammer
To knock out, punch the 3 connected parts with a
screwdriver and remove the pipe cover by hand
(See fig 5).
After marking the knockout hole, remove the burr and
mount the attached protective bush and guard material
for pass-through part in order to protect pipes and wires.
2. Pull the front panel downward.
freezing of drain at the cold district or a snowfall area, be
careful for drainage ability of drain.
The drainage ability increases when knockout holes on
the base pan are opened. (Open the knockout hole to
outside using a hammer (B), etc.).
(Fig. 4 - 7)
(Fig. 4, 5)
(Fig. 6)
(Fig. 7)
38XPS - 38XP-
2