3.3
ACCESS TO INSTALLER'S
PARAMETERS
For access to the installer's parameters,
press simultaneously the keys
for 5 seconds (3 fig. 14).
For example, the parameter PAR 23 is
visualised on the display of the control
panel in the following way:
The paramet er s scr oll for war ds and
backwards with the key
and
the default parameters can be changed
with the keys
and
.
The standard visualisation returns automa-
tically after 60 seconds, or by pressing one
of the control keys (2 fig. 14).
3.3. 1
Replacing the board or
RESETTING parameters
If the electronic board is replaced or reset,
it is necessary to configure PAR 1 and PAR
2 by associating the following values to
each type of boiler to be able to restart the
boiler:
BOILER
GAS
MODELS
METHANE
20
25
30
BF/BFT
35
LPG
20
25
30
35
METHANE
25
OF
30
LPG
25
30
FAST CONFIGURATION
and
PAR DESCRIPTION
1
Combustion configuration
2
Hydraulic configuration
3
Timetable 2 programmer
4
Pressure transducer disabler
and
5
Assignment of auxiliary relay AUX
(D.H.W. tank)
6
Luminous bar indicating presence
of voltage
7
Allocation of CR73 channels
8
-
9
-
10 Remote control option setting
11 Correction values external sensor
12 Backlighting duration
PAR 1
1
13 Modulating pump speed
2
3
4
5
6
D.H.W. - HEATING
7
PAR DESCRIPTION
8
9
20
D.H.W. minimum temperature
10
21
D.H.W. maximum temperature
11
22
Anti-legionella (only D.H.W. tank)
12
23
Boiler antifreeze
24
External sensor antifreeze
25
Climatic curve setting Zone 1
26
Climatic curve setting Zone 2
27
Minimum temperature Zone 1
28
Minimum temperature Zone 1
29
Minimum temperature Zone 2
30
Maximum temperature Zone 2
31
Maximum heating power
32
C.H. post-circulation time
33
Pump activation delay Zone 1
34
Re-ignition delay
35
Integrative sources activation threshold -- , 15 ... 80
36
D.H.W. post-circulation time
39
Saturation zone modulation
D.H.W. flowmeter
PARAMETERS INSTALLER
RANGE
UNIT OF
MEASUREMENT
-- = ND
1 ... 12
-- = ND
1 ... 14
1 = DHW + Recirc. pump
2 = DHW
3 = Recirculation pump
0 = Disabled
1 = Enabled
1 = Remote supply
2 = Recirculation pump
0 = Disabled
1 = Enabled
0 = Not assigned
1 = Circuit 1
2 = Circuits 1 and 2
-
-
1 = CR 73
2 = CR 53
3 = RVS
-5 ... +5
-- = Always
0 = Never
sec. x 10
1 ... 199
0 = Minimum
1 = Maximum
2 = Automatic
RANGE
UNIT OF
MEASUREMENT
10 °C ... PAR 21
PAR 20 ... PAR 62 OEM
0 = Disabled
1 = Enabled
0 ... +20
- 15 ... +5
3 ... 40
3 ... 40
PAR 64 OEM ... PAR 28
PAR 27 ... PAR 65 OEM
PAR 64 OEM ... PAR 30
PAR 29 ... PAR 65 OEM
30 ... 100
0 ... 199
0 ... 199
0 ... 10
0 ... 199
-- = Enabled
0 ... 100
INC/DEC
DEFAULT
UNIT
SETTING
=
=
"--"
=
=
"--"
=
=
1
=
=
1
=
=
1
=
=
1
=
=
1
-
-
-
-
-
-
=
=
1
°C
1
0
1
3
=
=
1
INC/DEC
DEFAULT
UNIT
SETTING
°C
1
30
°C
1
60
=
=
0
°C
1
3
°C
1
- 2
=
1
20
=
1
20
°C
1
20
°C
1
80
°C
1
20
°C
1
80
%
1
100
Sec.
10
30
10 sec.
1
1
Min.
1
3
°C
1
"--"
Sec.
1
0
%
1
100