sure, with the system cold, must be
between 1 and 1.5 bar. During system fil-
ling you are recommended to keep the main
switch turned OFF. Filling must be done
slowly so as to allow any air bubbles to be
bled off through the air valves. Should the
pressure have risen well above the limit
expected, discharge the over pressure by
opening the pressure-relief valve.
NB: The "BFT" versions the loading is
done by loading tap externally mounted by
the installer.
2.5. 1
Emptying the system (fig. 4)
Use the drain tap to empty the system (7).
Turn off the boiler before doing this.
2.6
FLUES/CHIMNEYS
A chimney or flue for the evacuation of the
combustion products into the atmosphere
must correspond to the requisites prescri-
bed by the laws in force. In particular, the
specific prescriptions of law relative to boi-
lers with natural draught in collective pipes
(type B) and those for boilers with forced
draught (type C) must be respected.
2.6. 1
Ducting of existing chimneys
To recover or duct existing chimneys, ducts
declared suitable for the purpose by the
manufacturer must be used, and the instal-
lation and use modalities indicated by the
said manufacturer must also be followed
as well as the prescriptions of Standard
UNI 10845.
2.7
INSTALLATION OF COAXIAL
DUCT (versions "BF - BFT")
2.7. 1
Accessories 60/100 (fig. 5)
The 60/100 coaxial duct is supplied on
request in kit code 8084811. The diagrams
For discharge types C12-C42, use the diaphragms supplied with the boiler:
- ø 84.0 for version "20" only when the length of the coaxial duct is less than 2 metres,
- ø 86.0 for version "25-35" only when the length of the coaxial duct is less than 1 metre,
- ø 87.5 for version "30" only when the length of the coaxial duct is less than 2 metres.
For discharge types C32, use the following diaphragms according to the length of the duct and without
additional curves:
Installations with vetrical
extension L. 200 code 8086908 *
"20 BFT" models
Diaphragm
Diaphragm
ø 84
ø 86
(code 6028622) (code 6028623)
L max = 4 m
L max = 5 m
"25 BF - 25 BFT - 30 BF - 35 BF" models
Diaphragm
Diaphragm
ø 86
ø 87,5
(code 6028623) (code 6028624)
L max = 2.5 m
L max = 4 m
* Minimum length of duct L = 1.3 m.
86
x + y = max 5,0 m per vers. "20"
x + y = max 3,5 m per vers. "25"
x + y = max 3,0 m per vers. "30-35-40"
IMPORTANT:
– Each additional 90° curve installed
reduces the available length by 1.0
metres.
– Each additional 45° curve installed
reduces the available length by 0.50
metres.
- The insertion of the condensation
collector (8) is obligatory for vertical
stretches of more than 1.3 metres.
KEY
1
Coaxial flue kit L. 810 code 8084811
2 a Extension L. 1000 code 8096103
2 b Extension L. 500 code 8096102
3
Vertical extension L. 200 code 8086908
4
Additional 90° curve code 8095801
6
Articulated tile code 8091300
7
Roof outlet terminal L. 1284 code 8091200
8
Vertical condensation collector L. 200 code 8092803
of fig. 5 illustrate some examples of diffe-
rent types of discharge modalities allowed
and the maximum lengths that can be rea-
ched.
2.7.2
Diaphragm for 60/100 coaxial
duct (fig. 5/a)
The boiler is supplied with a diaphragm of
84 (version 20 BFT), 86 (versions 25-35
Installations with vertical condensation
collector code 8092803 *
"20 BFT" models
Without
Diaphragm
diaphragm
ø 84
(code 6028622) (code 6028623)
----
L max = 3 m
"25 BF - 25 BFT - 30 BF - 35 BF" models
Without
Diaphragm
diaphragm
ø 86
(code 6028623) (code 6028624)
L max = 5 m
---
x
2
4
y
3
C42
max 5,0 m per vers. "20"
max 3,5 m per vers. "25"
max 3,0 m per vers. "30-35-40"
C12
BF/25 BFT) and 87.5 (version 30 BF).
The diaphragms 87.5 (code 6028824)
and 86 (code 6028623) can be reque-
sted separately.
Use the diaphragms according to the indi-
cations of fig. 5/a.
2.7.3
The ø 80/125 coaxial duct is supplied on
Diaphragm
Without
ø 86
diaphragm
L max = 5 m
---
Diaphragm
Without
ø 87,5
diaphragm
L max = 2.5 m
L max = 4 m
7
6
2
8
3
C32
1
Fig. 5
Accessories ø 80/125 (fig. 6)
Fig. 5/a