Design Of The Cables; How To Connect The Shield - Lenze L-force 9400 Serie Instrucciones Para El Montaje

Base de montaje
Ocultar thumbs Ver también para L-force 9400 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4
Electrical installation
Wiring

Design of the cables

4.3.2
Design of the cables
The cables used must comply with the approvals required for the location
ƒ
(e.g. UL).
It is imperative to comply with the regulations concerning minimum
ƒ
cross-sections of PE conductors. The cross-section of the PE conductor
must be at least as large as the cross-section of the power connections.
The effectiveness of a shielded cable is reached by:
ƒ
Providing a good shield connection through large-surface shield
contact.
Using only braided shields with low shield resistance made of tin-plated
or nickel-plated copper braid.
Using braided shields with an overlap rate > 70 % and an overlap angle
of 90 °.
Keeping unshielded cable ends as short as possible.
Use system cables or shielded cables for these connections:
Motor
ƒ
Motor holding brake (connected to optional motor brake control)
ƒ
Motor temperature monitoring
ƒ
The following connections need not be shielded:
DC bus
ƒ
4.3.3

How to connect the shield

Fig.7-3
Connect the shield to the shield sheet (graphics on the right: motor cable for device sizes
II and III)
42
E94AZPS004
EDK94ZPM113 DE/EN/FR/ES/IT 1.0

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

L-force e94azpm serie

Tabla de contenido