Functional description
USA
The operating and display panel with the integrated control unit is the central element of the
system. The touch−sensitive touch display enables flexible, country−specific adjustment of
the user interface via virtual keys and a variable display window. All messages are displayed
on the central display. The entire system is operated via a user interface with a user−friendly
design.
Twenty−three fix placed membrane keypads are positioned around the touch display for the
standard entries.
The system's operating status is displayed by 11 LEDs, and the control unit can be linked to a
PC via 2 interfaces(RS232, external CAN).
Technical Specification
Touch panel type
Display element
Active touch area (H x W)
Fixed operating elements
Status displays
Interfaces
Input voltage range
Output voltage to PRS 0002 A
Maximum current consumption
− standby mode
− alarm mode
Operating temperature
Storage temperature
Dimensions (H x W x D)
Weight
ST − FIR / PRM1 / deh
610−4.998.154.031
Resistive type, analog, 4wires, film on glass
320 x 240 dots LCD Touch screen with flexible keys
and displays
127,5 mm x 170 mm (5.0 x 6.7 inches)
23 fixed keys
11 LEDs
RS232, CAN extern
20 V DC . . . 30 V DC
+5V DC $4,5% / max. 500 mA output current
70 mA at 24 V DC
165 mA at 24 V DC
−5 _C . . . 50 _C
(23 _F . . . 122 _F)
−20 _C . . . 70 _C
190 mm x 404 mm x 60 mm (7.5 x 15.9 x 2.4 inches)
approx. 2000 g (70.6 ounces)
2 / 8
(−4 _F . . . 158 _F)
MPC 1000 A
A1 / 19.05.2005
MPC 1000 A