ALARMS
This control governs two types of alarms:
■ Serious Alarms cause the forced switching off of the ther-
mostat
■ Non-serious Alarms do not cause the forced switching off
of the thermostat, but disable possible critical functions
SERIOUS ALARMS
Alarm code
■ Code A01 = error of external air temperature sensor (in case
of on-board thermostat)
■ Code A02 = error of internal air temperature sensor (in case
of wall mounted thermostat and disconnected external air
temperature sensor)
NON-SERIOUS ALARMS
THERMOSTAT OFF
THERMOSTAT ON
■ Code A03 = water sensor error
■ Code A04 = external humidity probe error (only if a remote
temperature sensor is installed)
■ Code A05 = internal humidity probe error
N.B.: the alarm code is displayed only when the ther-
mostat is switched off
Installation and operation manual
14
MODBUS
The protocol implemented in the controller is Modbus RTU
(9600, N, 8, 2) on RS485
FUNCTIONS IMPLEMENTED
■ 0x03 : Read Holding Registers
■ 0x04 : Read Input Registers
■ 0x10 : Write Multiple registers
EXCEPTIONS IMPLEMENTED
Exception Code 02: Invalidate data address
LIST OF SUPERVISION PARAMETERS
ADDRESS REGISTER
Status
0
Speed
1
Air temperature
2
Humidity
3
Water temperature
4
P00: Confi guration
5
P05: DIN Confi g.
6
T. Active setpoint
7
T. User setpoint
8
LCD version
9
P09: DOUT1 Confi g.
10
11
P10: DOUT1 Logic
P11: DOUT2 Confi g.
12
P12: DOUT2 Logic
13
14
P14: AOUT1/2 Confi g.
Analog output 1
15
Analog output 2
16
Digital 1
50
Hourly programming
51
Setpoint - Cooling
52
Setpoint - Heating
53
Minimum Setpoint – Cool.
54
Maximum Setpoint – Cool.
55
Minimum Setpoint – Heat.
56
Maximum Setpoint – Heat.
57
Speed
58
Economy Correction
59
Modulating fan mode
60
TYPE U.O.M.
R
-
R
-
R
[°C/10]
R
%
R
[°C/10]
R
-
R
-
R
[°C/10]
R
[°C/10]
R
-
R
R
R
R
R
R
[%]
R
[%]
R/W
-
R/W
-
R/W
[°C/10]
R/W
[°C/10]
R/W
[°C/10]
R/W
[°C/10]
R/W
[°C/10]
R/W
[°C/10]
R/W
-
R/W
[°C/10]
R/W
-
FWEC3
Advanced plus electronic controller
FC66002765