Introduction

Display Messages

TANK PARAMETERS

The following tank parameters are displayed one at a time as the operator scrolls through the Top Level Menu.
• Product Volume,
• Product Height,
• Temperature Compensated Volume - (requires probes that have temperature measurement capability),
• Product Temperature (requires probes that have temperature measurement capability),
• Water Height (requires probes that have water measurement capability).
Pressing the Tank key allows the user to select which tank's data is displayed. If a parameter is not available for
any tank in the system, that display will not appear as you scroll through the menus. When viewing a display that is
available in one of the tanks, but is not available for the current tank, a "
that parameter.

ALARMS

When an alarm occurs, the console's internal beeper will activate, the front panel LED will flash red, and the top
line of the display will contain the alarm message. In the case of multiple alarms, the main display screen will
automatically scroll through the active alarms. Press the Silent key to switch off the internal beeper. The red LED
will continue to flash until the alarm condition is remedied.
When an alarm condition returns to the normal state the alarm will be removed from the list of alarms. If no alarms
are active, the LED will return to the Normal state (continuous green), the beeper will be switched off, and the top
line of the display status line will read ALL FUNCTIONS NORMAL.

Displayed Alarm Messages - All Consoles

• PROBE OUT (all probes) - If the console is not reliably communicating with the probe, the Probe Out alarm will
activate.
• INVALID HEIGHT (only probes that use two floats) - If the water float and the product float are too close
together to provide reliable height data, the Invalid Height alarm will activate.
• LOW TEMPERATURE (only probes with temperature option) - If the Probe is reporting a temperature lower
than -4° F (-19.8° C), the Low Temperature alarm will activate.
• NO TANKS CONFIGURED - This message displays in the top line of the display until at least one tank has
been configured in the Tank Setup menu. The front panel red LED will be flashing, but the console's internal
beeper will not be switched on.

Displayed Alarm Messages - Alarm Package Option

In addition to the basic alarms discussed above, additional tank alarms are available with the Alarm Package
option. Note, an active LOW TEMPERATURE alarm will inhibit any of the Alarm Package alarms.
• MAX PRODUCT - If the product volume exceeds the Max Product value entered in Tank Setup, the Max Product
Alarm will activate.
• OVERFILL - If there is a delivery in progress and the product volume exceeds the Overfill value entered in Tank
Setup, the Overfill alarm will activate closing the remote overfill alarm output relay. When the delivery stops, the
alarm will deactivate.
• LOW PRODUCT - If the product volume decreases to an amount less than the Low Product value entered in
Tank Setup, the Low Product alarm will activate.
• HIGH WATER (only probes with water measurement option) - If the water height in the tank exceeds the High
Water value entered in Tank Setup, the High Water alarm will activate.
" message will be displayed for
NO DATA
5
Display Messages