Panasonic S-22MU1E5 Instrucciones De Instalación página 15

Acondicionador de aire con sistema vrf - para refrigerante r410a
Ocultar thumbs Ver también para S-22MU1E5:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 171
Pana_indoor_336012_Eng.indb 23
3-22. Installing the Drain Pipe
(1) Prepare standard hard PVC pipe (O.D. 26 mm) for the drain
and use the supplied hose band to prevent water leaks.
(Fig. 3-64)
The PVC pipe must be purchased separately.
The transparent drain part on the unit allows you to check
drainage.
Twist tie
(4 ties, supplied)
Drain hose
Hard PVC pipe
Position to
Drain port
(equivalent to
insulation
fasten hose
O.D. 26 mm)
(supplied)
bands
(Field supply)
Drain hose
(supplied)
5
5
25
25
140
Hose band
(2 bands, supplied)
Unit
CAUTION
Attach so that the hose band fastener is on the side of the
drain port. (Fig. 3-64)
Attach the hose bands so that each is approximately 5 to 25
mm from the end of the supplied drain hose. (Fig. 3-64)
Do not use adhesive at the drain connection port on the
indoor unit.
Insert the drain pipe until it contacts the socket, as
shown in the figure above, then secure it tightly with the
hose band.
Do not use the supplied drain hose bent at a 90° angle.
(The maximum permissible bend is 45°.)
Tighten the hose clamps so their locking nuts face in the
horizontal direction.
Make sure that the drain port is not a downward gradient
from the joint section (may lead to abnormal noise).
N OTE
Make sure the drain pipe has a downward gradient (1/100 or
more) and that there are no water traps.
CAUTION
Do not install an air bleeder as this may cause water to
spray from the drain pipe outlet. (Fig. 3-65-1)
Air bleeder
Prohibited
Fig. 3-65-1
If it is necessary to increase the height of the drain pipe,
the section directly after the connection port can be
raised a maximum of 500 mm. Do not raise it any higher
than 500 mm, as this could result in water leaks.
(Fig. 3-65-2)
At least 1/100
300 mm or less (not a downward gradient)
500 mm or less
Good
Do not install the pipe with an upward gradient from the
connection port. This will cause the drain water to flow
backward and leak when the unit is not operating.
(Fig. 3-65-3)
Upward gradient
Prohibited
Do not apply force to the piping on the unit side when
connecting the drain pipe. The pipe should not be
allowed to hang unsupported from its connection to the
unit. Fasten the pipe to a wall, frame, or other support as
Unit:mm
close to the unit as possible. (Fig. 3-65-4)
Fig. 3-64
Support pieces
3-23. Checking the Drainage
After wiring and drain piping are completed, use the following
procedure to check that the water will drain smoothly. For this,
prepare a bucket and wiping cloth to catch and wipe up spilled
water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Remove the eyelet cap and through the opening, slowly
pour about 500 cc of water into the drain pan to check
drainage.
(3) Short the check pin (CHK) on the indoor control board and
operate the drain pump. Check the water flow through the
transparent drain port and see if there is any leakage.
CAUTION
Be careful since the fan will start when you short the pin on
the indoor control board.
(4) When the check of drainage is complete, open the check
pin (CHK) and remount the insulator and drain cap onto
the drain inspection port.
Wiring port
Water inlet
Eyelet cap
25
2011/01/12 13:55:52
Pana_indoor_336012_Eng.indb 24
3-24. Increasing the Fan Speed
■ For Short Circuit Connection
● The standard (before shipment) external static pressure is
shown in the table below.
● When using with a higher static pressure, it is necessary to
change to the high static pressure mode.
External static pressure
Fig. 3-65-2
Type
Standard (Pa)
High static pressure (Pa)
When using with high static pressure mode, set the indoor unit
control board as shown in Fig. 3-67.
Fig. 3-65-3
Indoor control board
Follow the below procedure while the unit is turned off.
(1) Open the cover of the electrical box and confirm that it is the
indoor unit control board.
Fig. 3-65-4
(2) Connect the short circuit connector to the short circuit pin
TP3 (2P: Yellow) of the indoor unit control board.
In case of wired remote control setting, do not use the short
circuit connector.
External static pressure's
upper limit in high static
pressure mode
Standard external
static pressure's
H
upper limit
L
H
L
Lower limit airflow
3
Airflow (m
S-22MM1E5
5
40
HH
30
H
L
20
10
L
H
HH
0
0
4 5 6 7 8 9 10 11
Airflow (m
3
/minute)
Fig. 3-66
S-36MM1E5
50
HH
40
H
30
L
22
28
36/45/56
20
10
15
15
H
10
30
30
40
L
0
4 5 6 7 8 9 10 11 12
Airflow (m
3
/minute)
White Yellow Red
S-56MM1E5
60
HH
TP6 TP3 TP1
50
H
40
L
30
HH
20
H
L
10
0
7 8 9 10 11121314 15
Fig. 3-67
3
Airflow (m
/minute)
Rated external static
HH
pressure in high static
pressure mode
Lower static pressure
in high static pressure
mode
HH
Rated external static
pressure at shipment
Upper limit airflow
/minute)
S-28MM1E5
5
40
HH
30
H
L
20
H
10
L
HH
0
0
4 5 6 7 8 9 10 11
12
3
Airflow (m
/minute)
26
2011/01/12 13:55:53
S-45MM1E5
60
50
5
5
HH
40
H
L
30
20
HT
HH
HH
H
10
L
0
0
0
5 6 7 8 9 10 11 12 13
Airflow (m
3
/minute)
5
0
Fig. 3-68

Publicidad

Tabla de contenido
loading

Tabla de contenido