Panasonic S-22MU1E5 Instrucciones De Instalación página 29

Acondicionador de aire con sistema vrf - para refrigerante r410a
Ocultar thumbs Ver también para S-22MU1E5:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 171
Pana_indoor_336012_Eng.indb 51
Air filter
The air filter collects dust and other particles from the air and
should be cleaned at regular intervals as indicated in the table
below or when the filter indication ( ) on the display of the
remote control unit (wired type) shows that the filter needs
cleaning. If the filter gets blocked, the efficiency of the air
conditioner drops greatly.
Type
U1, Y1
T1
F1, M1, E1*
(Depends on filter
Period
6 months
2 weeks
specifications)
*Low Silhouette Ducted, Slim Low Static Ducted, High
Static Pressure Ducted Type (F1, M1, E1):
An air filter is not provided with this air conditioner at the time of
shipment. To get clean air and to extend the service life of the
air conditioner, an air filter must be installed in the air intake.
For installation and cleaning the air filter, consult your dealer or
service center.
N OT E
The frequency with which the filter should be cleaned depends
on the environment in which the unit is used.
<How to clean the filter>
1. Remove the air filter from the air intake grille.
2. Use a vacuum cleaner to remove light dust. If there is sticky
dust on the filter, wash the filter in lukewarm, soapy water,
rinse it in clean water, and dry it.
<How to remove the filter>
4-Way Cassette Type (U1):
1. Use a screwdriver to remove the bolt screw on each side
for the two latches. (Be sure to reattach the two bolt screws
after cleaning.)
2. Slide the latches of the air intake grille in the direction of the
inside to open the grille.
3. The air intake grille opens downward.
CAUTION
● When cleaning the air filter, never remove the safety
chain. If it is necessary to remove it for servicing and
maintenance inside, be sure to reinstall the safety chain
securely (hook on the grille side) after the work.
● When the filter has been removed, rotating parts (such
as the fan), electrically charged areas, etc. will be
exposed in the unit's opening. Bear in mind the dangers
that these parts and areas pose, and proceed with the
work carefully.
4. Push the side of the air filter marked with the indication
arrow
and pull it toward you. The air filter will be
disengaged.
Air intake grille
Latch
Air filter
Screw
4-Way Cassette 60x60 Type (Y1):
1. Use a screwdriver to remove the bolt screw on each side
for the two latches. (Be sure to reattach the two bolt screws
after cleaning.)
2. Press on the two latches of the air intake grille with your
thumbs in the direction of the arrow to open the grille.
3. Open the air intake grille downward.
CAUTION
● When cleaning the air filter, never remove the safety
chain. If it is necessary to remove it for servicing and
maintenance inside, be sure to reinstall the safety chain
securely (hook on the grille side) after the work.
● When the filter has been removed, rotating parts (such
as the fan), electrically charged areas, etc. will be
exposed in the unit's opening. Bear in mind the dangers
that these parts and areas pose, and proceed with the
work carefully.
4. Remove the air filter attached to the air intake grille.
Latch
Safety
chain
Air intake
Screw
grille
Air filter
Ceiling Type (T1):
1. Take hold of the finger-hold on the air intake grille and
press it to the rear, and the grille will open downward.
2. Take hold of the finger-hold on the air filter, pull it toward
you.
Air intake grill
finger-hold
Screw
Air filter
Hook
Screw
Latch
Air filter finger-hold
* Take hold of the finger-hold on the air filter, pull it toward you.
Safety cord
53
2011/01/12 13:56:10
Pana_indoor_336012_Eng.indb 52
CAUTION
● Certain metal edges and the condenser fins are sharp
and may cause injury if handled improperly; special care
should be taken when you clean these parts.
● Periodically check the outdoor unit to see if the air outlet
or air intake is clogged with dirt or soot.
● The internal coil and other components must also be
cleaned periodically. Consult your dealer or service
center.
Care: After a prolonged idle period
Check the indoor and outdoor unit air intakes and outlets for
blockage; if there is a blockage, remove it.
Care: Before a prolonged idle period
Operate the fan for half a day to dry out the inside.
Disconnect the power supply and also turn off the circuit
breaker.
Clean the air filter and replace it in its original position.
Outdoor unit internal components must be checked and
cleaned periodically. Contact your local dealer for this
service.
Air filter finger-hold
Air intake grill
54
2011/01/12 13:56:11