Pana_indoor_336012_Eng.indb 43
7-2. How to Install the Ceiling Panel
(1) Removing the air-intake grille
1) Remove the 2 screws on the latch of the air-intake
grille. (Fig. 7-1) (Reattach the air-intake grille after
installation of the ceiling panel.)
2) Slide the air-intake grille catches in the direction
shown by the arrows 1 to open the grille. (Fig. 7-1)
Air-intake grille
Ceiling panel
1
1
Air-intake
grille hinge
3) With the air-intake grille opened, remove the grille
hinge from the ceiling panel by sliding it in the direction
shown by the arrow 2. (Fig. 7-2) (Reattach the air-
intake grille after installation of the ceiling panel.)
2
(2) Removing the corner cover
Slide the corner cover in the direction of the arrow 1 and
remove it.
1
Push to
disengage
Corner cover
Ceiling panel
Corner cover
2
Slide
Strap
(3) Installing the ceiling panel
The power must be turned ON in order to change the
flap angle. (Do not attempt to move the flap by hand.
Doing so may damage the flap.)
1) Hang the temporary latches on the inside of the ceiling
panel to the receptacle on the unit to temporarily
attach the ceiling panel in place. (Fig. 7-4)
The ceiling panel must be installed in the correct
direction relative to the unit. Align the REF. PIPE and
DRAIN marks on the ceiling panel corner with the
Screw
correct positions on the unit.
Latch
When removing the ceiling panel, push the temporary
latches outward while holding the ceiling panel.
(Fig. 7-4)
Receptacle on the
Push to disengage
main unit
Fig. 7-1
Temporary latch
Temporary latch
2) Align the panel installation holes and the unit screw holes.
3) Tighten the supplied washer head screws at the
4 panel installation locations so that the panel is
attached tightly to the unit. (Fig. 7-5)
Drain tube corner
Refrigerant tube
corner
Fig. 7-2
Ceiling panel
DRAIN mark
REF. mark
Washer head screws
4) Check that the panel is attached tightly to the ceiling.
At this time, make sure that there are no gaps
between the unit and the ceiling panel, or between the
ceiling panel and the ceiling surface. (Fig. 7-6)
Do not allow gaps.
Main unit
Ceiling surface
Ceiling panel
If there is a gap between the panel and the ceiling,
leave the ceiling panel attached and make fine
adjustments to the installation height of the unit to
eliminate the gap with the ceiling. (Fig. 7-7)
Fig. 7-3
Make fine adjustments by a wrench
or other tool to the installation height
of the unit to eliminate the gap with
the ceiling through the hole of the
corner cover.
45
2011/01/12 13:56:00
Pana_indoor_336012_Eng.indb 44
CAUTION
If the screws are not sufficiently tightened, trouble
such as that shown in the figure below may occur.
Be sure to tighten the screws securely.
Air leakage
Air leakage
from ceiling panel
Staining
Condensation, water leakage
If a gap remains between the ceiling surface and the
ceiling panel even after the screws are tightened,
adjust the height of the unit again.
Adjust so that there
are no gaps.
If there is no affect to the horizontal
of the unit and drain tube, adjustment
Fig. 7-4
to the installation height of the unit
can be made through the hole of the
ceiling panel corner.
(4) Wiring the Ceiling Panel
1) Open the cover of the electrical component box for
control PCB.
2) Connect the 22P connector (white) from the ceiling
panel to the connector on the control PCB in the unit
electrical component box. In this case, expose the
cutout section of the tube for the wiring protection to
the outside from the electrical component box and fix it
with the clamper attached to the electrical component
box.
If the connectors are not connected, the Auto Flap
will not operate. Be sure to connect them securely.
(If not connected completely, "09" will be displayed
on the remote controller.)
Fig. 7-5
Check that the wiring connector is not caught
between the electrical component box and the
cover.
Check that the wiring connector is not caught
between the unit and the ceiling panel.
Electrical component
box cover
Fig. 7-6
Screws (2 locations)
Cutout section of the tube
for the wiring protection
Clamper
Ceiling panel side
Main unit side
Fig. 7-7
(5) How to Attach the Corner & Air-Intake Grille
A. Attaching the corner cover
1) Check that the safety cord from the corner cover is
fastened to the ceiling panel pin, as shown in the figure
below.
2) Use the supplied screws to attach the corner cover to the
ceiling panel.
Place the corner cover so that the 3 tabs fit
into the holes in the ceiling panel.
Pin
Then fasten it in place with the supplied
screws.
B. Attaching the air-intake grille
To install the air-intake grille, follow the steps for
"Removing the grille" in the reverse order. By rotating
the air-intake grille, it is possible to attach the grille onto
the ceiling panel from any of 4 directions. Coordinate the
directions of the air-intake grilles when installing multiple
units, and change the directions according to customer's
requests.
When attaching the air-intake grille, be careful that the
flap lead wire does not become caught.
Be sure to attach the safety cord that prevents the air-
intake grille from dropping off to the ceiling panel unit as
shown in the figure below.
With this ceiling panel, the directions of the air-intake grille
lattices when installing multiple units, and the position
of the label showing the company name on the corner
panel, can be changed according to customer's requests,
as shown in the figure below. However, the wireless signal
receiver can only be installed at the refrigerant-tubing
corner of the ceiling unit.
Hole for ceiling panel hook
Hook that prevents the grille from dropping
Drain pipe side
Locations of air-intake
grille hinges at the
factory shipment
Wiring chart
* The grille can be
(Direction that the unit
installed with these
faces has been changed to
hinges facing in any of
facilitate explanation.)
4 directions.
Electrical
component box
Ceiling panel
wiring connector
Fig. 7-8
46
2011/01/12 13:56:00
Refrigerant tube side
Wireless signal receiver
* Only this area
is possible for
installation.
Can be installed
rotated 90º
Fig. 7-9