PROHEAT II SERIES · AIR/WATER SYSTEM
F87
Test time
F90
Displays the card model
F91
Displays the version of the card software
F92
Shows the display model.
F93
Shows the version of the display model.
F94
Displays the card ID
F99
Automatic regulator test
End
F00
Exit
* Observation1:When F24=1, this means there is only one circuit. Therefore, none of the
System 2 inputs/outputs can be used. And no error codes will be displayed.
6.4.
STARTING BASIC OPERATION
6.4.1. OPERATING MODE
The regulator has 4 operating modes, depending on the heat pump model: Cool, Heat,
Auto and Manual selection of the operating mode. The available operating mode is controlled
by parameter F29.
F29=0, only Auto mode (C/H).
F29=1, only Heat mode (C/H).
F29=2, only Cool mode (C/H).
F29=3, Manual selection of the operating mode (M).
In the Cool mode, the machine starts cooling when the probe temperature is higher than
the "Temperature setpoint + Temperature differential" and it stops cooling when the
temperature is lower than the "Setpoint temperature - Differential temperature".
In the Heat mode, the machine starts heating the water when the probe temperature is
lower than the "Temperature setpoint + Temperature differential" and it stops heating when
the temperature is higher than the "Setpoint temperature - Differential temperature".
In the Auto mode, the machine starts cooling when the probe temperature is higher than the
"Temperature setpoint + Auto mode temperature differential" and it stops cooling when the
© FLUIDRA 2016 ALL RIGHTS RESERVED. PROPRIETARY DOCUMENT.
0 -- 999
OFF
Time
This function
can activate
all the relays;
please do not
use this
function
while the
regulator is
running.
ENGLISH
The regulator will stop
of the accumulate time
is longer than the test
time and the error code
"A99" will be displayed.
OFF means no test time