6.4.6. WATER TREATMENT PUMP CONTROL

The user can choose whether to control the water treatment pump or not (F40). 0 means that
it is not controlled and 1 means that the pump is controlled. When the water pump is running,
the compressor starts a certain time later (F41) and when the compressor stops, the water
treatment pump stops a certain time later (F42). The compressor will not start until the water
treatment pump reaches the F41 time. When the machine stops, the pump will continue the
F43 stop F44 start cycle.

6.4.7. FAN OPERATING CONDITIONS

When F27=-10, the fan will run at normal speed. In the PROHEAT II model, the fan will rotate
at this fixed speed.
When F27≠-10,
If the ambient temperature ≤F27(20ºC), the fan will run at maximum speed.
If F27 (20ºC)
Ambient temperature<F28 (45ºC), the fan will run at minimum speed.
<
If ambient temperature ≥F28 (45ºC), the fan will run at maximum speed.
The PROHEAT II machines run at normal speed F27=-10ºC.

6.4.8. REMOTE SWITCH

When the remote switch is closed:
If the unit is running. The unit works normally
If the unit is stopped. The unit stops.
When the remote switch is open:
If the unit is running. The unit stops and the screen display "OFF".
If the unit is stopped. The unit stops.