9) VE.Direct port RX pin mode (setting 57)
Value
Description
0
Remote on/off (default). Can be used for on-off control by a VE.Bus BMS (instead of
connecting the BMS to the remote on-off port.
VE.Direct non-inverting remote on/off cable needed. (ASS030550310)
1
No function.
2
The RX pin can de-energize the relay (relay off), if relay function 10 of setting 11 has
3
been set (see note 5, value 10). The load control options (setting 35) remain valid.
In other words, a AND function is created: both the load control and the RX pin must
be high (value=2) or low (value=3) to energize the relay.
10) VE.Direct port TX pin mode (setting 58)
Value
Description
0
Normal VE.Direct communication (default)
For example to communicate with a Color Control panel (VE.Direct cable needed)
1
Pulse every 0.01kWh
2
Light dimming control (pwm normal) TX digital output cable needed
(ASS0305505500)
3
Light dimming control (pwm inverted) TX digital output cable needed
(ASS0305505500)
4
Load control mode: theTX pin switches according to load control mode, see note 7.
TX digital output cable (ASS0305505500) needed to interface to a logic level load
control port.
11) Press SELECT: the text "" will blink, press SELECT again to reset to original
factory settings. The charger will re-boot. The history data will not be affected (kWh counter,
etc).
12) Press SELECT: the text "" will blink, press SELECT again to erase the history data
(kWh-counter, etc). Note that this takes a few seconds to complete.
Note: any setting change performed with the pluggable LCD display or via Bluetooth
will override the rotary switch setting. Turning the rotary switch will override prior
settings made with the pluggable LCD display or via Bluetooth.
Warning: Some battery manufacturers do recommend a constant current equalization
period, and others do not. Do not use constant current equalization unless
recommend by the battery supplier
16
.