Modbus modbus register map

Group name
Tag name
Setup
Baud rate
Setup
Modbus mode
Setup
Data order
Setup
Parity
Setup
Stop bits
Setup/Addresses
Network card address
Setup
Modbus card name
Network Timing
READ TIMEOUT
Network Timing
REG WRITE TMO
Network Timing
FILE WRITE TMO
Network Timing
FILE PREP TMO
Setup/Addresses
Device address
Setup/Addresses
Select device
Diagnostics
FUNCTION CODE
Diagnostics
NEXT STATE
Diagnostics
INT BAUD RATE
Register # Data type
Length R/W Discrete
40001
Unsigned integer 1
40002
Unsigned integer 1
40003
Unsigned integer 1
40004
Unsigned integer 1
40005
Unsigned integer 1
40006
Unsigned integer 1
40007
String
8
40015
Unsigned integer 1
40016
Unsigned integer 1
40017
Unsigned integer 1
40018
Unsigned integer 1
40019
Unsigned integer 1
40020
Unsigned integer 1
40021
Unsigned integer 1
40022
Unsigned integer 1
40023
Unsigned integer 1
Min/Max range Description
Range
R/W 0/1/2/3/4
R/W 0/1
R/W 0/1
R/W 2/0/1
R/W 1/2
R/W
0/246
R/W
R/W
1000/30000
R/W
3000/30000
R/W
5000/30000
6000/30000
R/W
0/246
R/W
0/30
R/W
0/65535
R
0/65535
R
0/1/2/3/4
Baud rate selection (0=9600; 1=19200;
2=38400; 3=57600; 4=115200)
Modbus mode (0=RTU; 1=ASCII)
Register Data order (0=Little Endian
register order; 1=Big Endian register
order)
Modbus parity (0=Even; 1=Odd;
2=None)
Number of stop bits (1 or 2)
Modbus address for the Modbus card
(1 to 246)
Location string of the network card
Register read timeout setting (ms)
Register write timeout setting (ms)
File write timeout setting (ms)
File write timeout setting (ms)
The selected Modbus address of the
device (1 to 246)
Select the device to view/set Modbus
address (1 to 30)
Function code used in the menu
system
Next state value used in the menu
system
Baud rate selection (0=9600; 1=19200;
2=38400; 3=57600; 4=115200)