SETTING MICROSWITCHES
DIP 1
CHECKING THE ROTATION DIRECTION OF
THE MOTOR (ON) (POINT C)
DIP 2
TIMING SETTING TOTAL (ON) (STEP D)
DIP 2-1 TIMING SETTING OF PEDESTRIAN GATE
OPENING (DIP 2 ON, THEN DIP 1 ON) (STEP D)
OPERATING MICROSWITCH
DIP 3
Pause time before the automatic closing (ON)
DIP 4
Jogging radio receiver (OFF) - automatic (ON)
DIP 5
Single impulse command (K BUTT) jogging (OFF) - automatic (ON)
DIP 6
Photocells always active (OFF) - Photocells only when the gate
closes (ON)
DIP 7
DIP 8
Pre-blinking (ON) - Normal blinking (OFF)
DIP 9
Pedestrian automatic closing operation (ON)
DIP 10 Current sensor enabled (ON) disabled (OFF)
LED SIGNALS
DL1
photocells contact (NC)
DL2
stop signal (NC)
DL3
opening limit switch contact (NC)
DL4
closing limit switch contact (NC)
DL5
programming started
DL6
gate on opening "OPEN" (green)
DL7
gate on closure "CLOSE" (red)
DL8
manual release safety device (NC)
DL9
Encoder operation check (not present on K800 24V)
DL10
triggering control of current sensor
DL11
control of storage/erasing of radio codes
C -
MOTOR DIRECTION CHECK
This control is carried out to facilitate the installation of the system or any
possible future control.
1 - After you have ensured the correct positioning of the limit switch
plates manually move the gate to half open position;
2 - Put DIP 1 in the ON mode => The LED DL5 starts blinking;
3 - Press the PROG button and hold it (the gate now is controlled in a
dead man mode: open, stop close stop open) => THE RED LED DL7
«CLOSE» comes on and the gate starts closing (if it does not close,
invert the wires of the motor) until it reaches the limit switch of the close
position (if the gate and motor do not stop, release the PROG button
and invert the position of the J11 connector); after 3 sec of continuous
travel, open or close, speed will automatically revert to slow. Adjust slow
speed setting the trimmer LOW SPEED to the required value.
4 - Press the PROG button and hold it => THE GREEN LED DL6 «OPEN»
comes on and the gate opens until it reaches the limit switch for
opening position;
5 - At the end of the control, position DIP1 on mode OFF. The LED DL5
turns off, signalling you exit from the control.
NOTE: During the above operation the current sensor and the safety circuit
are not operative.
D -
TIME PROGRAMMING
TOTAL SETTING
The programming can be carried out regardless of the gate position.
1 - Put DIP 2 in the ON mode=> The LED DL5 emits short blinkings;
2 - Push button PROG. => the gate closes. 2 seconds after the gate closed,
it opens automatically. When the opening cycle Is concluded, the gate
stops. Wait as long as you want the gate to remain open (excluded by
DIP3 OFF);
3 - Push button PROG. to operate the gate closing (also the pause time
count stops before the automatic closing - max. 5 minutes);
4 - The gate stops when the closing cam is reached;
5 - Position DIP 2 back on mode OFF when the programming is concluded.
SETTING OF PEDESTRIAN GATE
With the gate closed and the travel end switch triggered:
1 - Set DIP 2 on ON (led DL5 flashing quickly), then DIP 1 on ON (led DL5
flashing slowly).
2 - Depress the pedestrian pushbutton (COM-PED.BUTT.)
gate opens.
3 - Depress the pedestrian pushbutton to stop the motion (thus defining the
pedestrian opening of the gate).
4 - Wait the time that wants the gate remains opened (excludible with DIP9
on OFF), then depress the pedestrian pushbutton to start closure.
5 - On triggering of closure end stroke switch, set DIP1 and 2 on OFF.
During setting the safety circuits are operative, and triggering will stop the
procedure (led from flashing to steady).
To repeat the setting procedure, position DIP 1 and 2 on OFF, then close
the gate and repeat the above procedure.
O
PERATION OF THE OPERATING ACCESSORIES
OPENING BUTTON (with timer function) COM-OPEN
When the gate is standstill, the button controls the opening movement. If
the button Is operated while the gate Is closing, It opens the gate again.
TIMER FUNCTION
This function can be useful in rush hours, when vehicle traffic is slow (e.g.
entry/exit of workers, emergencies In residential or parking areas, and,
temporary, for removals).
APPLICATION MODES
If you connect a switch and/or a daily/weekly timer (at place or in parallel
to the opening button N.O. "COM-OPEN"), you can open the automation
and keep it open as long as the switch is operated or the clock is activated.
When the automation is open, all operating functions are inhibited.
If the automatic closing Is selected, the automation Immediately closes
when the switch Is released or at the time previously set; If not, you need
to use a command.
CLOSING BUTTON (COM-CLOSE)
It operates the closing movement when the gate is standstill.
JOGGING OPERATION BUTTON (COM-K BUTTON)
If DIP5 is OFF => It cyclically commands open-stop-close-stop-open-
etc.
If DIP5 is ON =>
It opens the gate when this is closed. If this button is
operated while the gate is opening, It has no effect. It
closes the gate If is operated when this is open and
opens the gate If is operated while this is closing.
RADIO TRANSMITTER
If DIP4 is OFF => It cyclically commands open-stop-close-stop-open-
etc.
If DIP4 is ON =>
It opens the gate when this is closed. If it is operated
while the gate is opening, It has no effect. If it is
operated when the gate Is open, it closes the gate. If it
is operated while the gate is closing, it opens the gate
again.
AUTOMATIC CLOSING
Pause times before the automatic closing of the gate are set with the timing
procedure.
The max. pause time is 5 minutes.
DIP3 (ON started) can start or stop the pause time.
PUSHBUTTON PEDESTRIAN OPENING (COM-PED.BUTT.)
Control for partial opening and closure.
During the opening stroke, the pause or the pedestrian opening, it is
possible to select open from any control connected to the card KS 24V.
Through the DIP5 it is possible to select the pedestrian pushbutton mode
of operation.
When DIP5 on OFF => Cyclic sequence of open-stop-close-stop and s.o.
When DIP5 on ON =>
30