2. Insert screws through the holes in the mounting brackets into the wall location.
The Secure Router 2330 has two internal, non-removable fans. Allow sufficient clearance for
maintenance and for proper airflow. Keep cable bundles clear of the intake and exhaust
vents.
Installing the Secure Router 2330/4134 in an equipment
rack
Required tool: Phillips screwdriver for attaching brackets to the switch.
• The Secure Router 2330 requires one rack unit (1.75 inches, 44.45 millimeters)
• The Secure Router 4134 requires two rack units (3.5 inches, 88.90 millimeters)
• The rack must be bolted to the floor, and braced if necessary.
• The rack must be grounded to the same grounding electrode used by the power service
in the area. The ground path must be permanent and must not exceed 1 ohm of resistance
from the rack to the grounding electrode.
• Ensure that the mounting brackets are firmly installed on the chassis.
• Ensure that you have appropriate antistatic materials.
Electrostatic alert:
Risk of equipment damage
Always wear an antistatic wrist strap connected to an ESD jack to prevent damage from
electrostatic discharge.
• Avaya recommends that you have two people ready to help lift the Secure Router 4134
into the equipment rack and securing it.