Installing The Secure Router 2330/4134 In An Equipment Rack - Avaya 2330 Manual Del Usario

Ocultar thumbs Ver también para 2330:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

English
2. Insert screws through the holes in the mounting brackets into the wall location.
The Secure Router 2330 has two internal, non-removable fans. Allow sufficient clearance for
maintenance and for proper airflow. Keep cable bundles clear of the intake and exhaust
vents.
Installing the Secure Router 2330/4134 in an equipment
rack
Required tool: Phillips screwdriver for attaching brackets to the switch.
• The Secure Router 2330 requires one rack unit (1.75 inches, 44.45 millimeters)
• The Secure Router 4134 requires two rack units (3.5 inches, 88.90 millimeters)
• The rack must be bolted to the floor, and braced if necessary.
• The rack must be grounded to the same grounding electrode used by the power service
in the area. The ground path must be permanent and must not exceed 1 ohm of resistance
from the rack to the grounding electrode.
• Ensure that the mounting brackets are firmly installed on the chassis.
• Ensure that you have appropriate antistatic materials.
Electrostatic alert:
Risk of equipment damage
Always wear an antistatic wrist strap connected to an ESD jack to prevent damage from
electrostatic discharge.
• Avaya recommends that you have two people ready to help lift the Secure Router 4134
into the equipment rack and securing it.
16