MOUNTING INSTRUCTIONS (Fig. 1)
1. Lift off mounting plate
as shown.
2. Fasten the mounting plate to the ceiling in the required position using
mounting holes
.
3. Specified mounting height: min. 2.5 m - max. 5.0 m.
4. The detection pattern can be adjusted by up to ± 15° (max 30°) by rotation
of the mounting plate prior to tightening the screws.
5. Strip cable for 5 cm and pull it through the cable entry hole
6. Wire the detector and select the appropriate processing options as shown
in Fig. 3. and replace the sensor module
7. To mount the sensor module to the mounting plate use the screw
which is placed for transport in the mounting plate.
The curtain directions 1-9 clockwise
(Curtain no. 5 is the centercurtain).
SITING THE DETECTOR (Fig. 2)
Install the detector so that the expected movement of an intruder will be across
the fields of view. This is the direction best detected by PIR detectors.
Avoid possible false alarm sources such as:
*
Direct sunlight onto the detector.
*
Heat / cold sources in a field of view (heaters, air conditioning, radiators,
etc.).
*
Moving objects in the field of view (fans, pets, etc.).
Increase of mounting heights beyond the specified (2.5 to 5.0 m) range will
reduce sensitivity.
Note: The arrow (Fig. 1
and Fig. 2) indicates the centre curtain direction and
the active direction when switch 4 "ON".
Switch 1: Programming the Control Voltage (CV):
" ON " Inversed logic , a Low voltage is needed to enable WALK TEST and
LATCH functions.
" OFF " Standard Aritech logic, a High voltage is needed to enable WALK TEST
and LATCH functions.
Switch 2: Programming the LED:
" ON " enables the LED on the detector at all times.
" OFF " puts the LED under the control of the WALK TEST and LATCH input.
Switch 3: Programming the processing:
" ON " enables Bi-curtain processing designed for harsh environment.
Note: Bi-curtain is used to reduce the possibility of false alarms. It looks
for signal verification and requires the intruder to be seen in two curtains
for an alarm.
" OFF " provides the standard Aritech 4D processing .
Switch 4: Programming the detection pattern:
" ON " provides a 180° field of view for special applications.
" OFF " gives the normal 360° field of view.
ALARM MEMORY
Note: First set the Control Voltage ("CV") by switch 1 (see Fig. 3).
(For example: switch 1 = "-", then "CV" = 0 Volt = "Low").
Connect "CV" to terminal 9 when the system is armed. When system is disarmed,
disconnect the "CV". If an alarm has occured during the armed period, the
detector or detectors which gave the alarm are indicated by a flashing LED. Re-
applying the "CV" (re-arming the system) will reset LED indication and memory.
REMOTE ENABLE/DISABLE OF WALK TEST LED
To walk test the detector, the "CV" to terminal 9 (latch) must be disconnected.
Connect "CV" to terminal 10. The detector's LED will now light and go out again
as the alarm relay opens and closes, making possible walk testing.
Note 1: Enabling the walk test will not clear alarm memory. After disarming the
system after an alarm, you may switch to walk test. When you switch back out
of walk test, the indication of memorized alarms will re-appear. Only when "CV"
is re-applied to terminal 9 (ie. system is re-armed) will LEDs and memory be
cleared.
Note 2: To enable the walk test LED without a remote "CV" input, connect a link
between terminal 2 and 10.
ACCESS TO THE MIRROR INSIDE THE SENSOR MODULE
This access is only required when masking individual curtains.
Undo screw
and open the sensor module
accessible now.
English
and strain relief.
.
, are indicated in the mountingplate.
(Fig. 1). The two mirrors are
SELECTING THE COVERAGE PATTERNS
Mask the appropriate mirror curtains with the adhesive labels provided and
reassemble the sensor module.
For example: see Fig. 5 for mirror curtain coverage pattern corresponding to
curtain 4 & 8 masked.
Technical data:
Input power
Peak to peak ripple
Current consumption
Normal operation
&
Alarm
Target speed range
Alarm output
Alarm time
Tamper output
Temperature limit
Relative humidity
Size
Weight
Number of zones
Max. detection range
Housing meets
(with sealed cable entry)
- 2 -
EV669
EV666
7-15 V
(12 V
nom.)
7-15 V
2 V max. (at 12 V
)
2 V max. (at 12 V
6 mA
10 mA
11 mA max.
11 mA max.
min. 0.3 - max. 3.0 m/s
min. 0.3 - max. 3.0 m/s
100 mA at 28 V
100 mA at 28 V
Form A (NC),
Form C
voltage free relay
switch over contact
min 2.5 sec.
min 2.5 sec.
100 mA at 28 V
100 mA at 28 V
-18 °C to +55 °C
-18 °C to +55 °C
max. 93%
max. 93%
Ø 138 x 68 mm
Ø 138 x 68 mm
190 g
190 g
18
18
10 m radius;
10 m radius;
(20 m diameter)
(20 m diameter)
IP30 IK02
IP30 IK02
(12 V
nom.)
)