Select the Save Mode You Want to Use
Save modes enable you to specify how buttons on the control unit work. For example, adjustments to a zone's
settings can be temporary or saved for the current scene. Buttons can also be disabled to prevent accidental
changes.
Select Sd
2
ZONE 5
ZONE 6
Code
Stands for
Sd
Save by Default
Sb
Save by Button
Sn
Save Never
4S
Four Scenes
bd
Button Disable
16- and 24-Zone GRX Control Units
The 16 and 24 zone GRAFIK Eye control units offer an expanded number of zones that can be controlled from a
single wall station. The zone intensity LEDs on the GRX-4x16 or GRX-4x24 will display the light level of a set of
eight zones at a time. Other sets of zones may be displayed and controlled by pressing the Zone Select Button.
Addressing
The GRX-4x16 and the GRX-4x24 control units take multiple, consecutive addresses. The GRX-4x16 control unit
takes up two consecutive addresses, and the GRX-4x24 control unit requires three. To ensure there are sufficient
addresses available, any GRX-4x16 and/or GRX-4x24 control units in the system should be addressed first.
Assigning Zones
When assigning zones use the chart below as a guide to see how zones are displayed on the Circuit Selector. The
chart is for a 24-zone control unit, which uses three addresses. A 16-zone control unit uses only two addresses.
Control Unit Addresses
A1, A2, A3
A2, A3, A4
.
.
.
.
.
.
A6, A7, A8
R
3
Select
save mode
FADE
TEMPORARY
ZONES
M S
MASTER
Enter
(exit)
setup
mode
Description
C hanges to a zone's intensity/shade position or fade time are saved for the current scene.
To make temporary adjustments in Sd mode, refer to page 19. Typical user: Home theater
owner.
T EMPORARY ZONES LED is normally ON and all intensity/shade position and fade changes
are temporary unless the TEMPORARY ZONES LED is turned OFF with the TEMPORARY
ZONES button. Typical user: Restaurant manager.
T EMPORARY ZONES LED is permanently ON and cannot be turned OFF. In this mode, all
intensity changes are temporary. Typical user: Lighting designer.
A llows only the four SCENE buttons, OFF button, IR receiver, and MASTER 5 or 6 buttons
to operate. All other buttons on the control unit are disabled. Typical use: Rented meeting
space.
A ll buttons on the control unit are disabled. IR receiver and wallstations are still functional.
(Setup mode is still accessible by repeating Step 1.) Typical use: Public space.
Zones on Control Unit
1-8
9-16
17-24
1-8
9-16
17-24
.
.
.
.
1-8
9-16
17-24
To select the save mode you want to use:
1. Enter setup mode. Press and hold the SCENE 1 and
OFF buttons for about three seconds until scene LEDs
start cycling.
2. Select Sd. Press the FADE 5 button until Sd is dis-
played in the FADE window.
3. Select save mode. Press the MASTER 5 or 6
button to scroll through the save modes and select
one. Refer to the save mode descriptions in the table
1
4
below.
,
4. Exit setup mode. Press and hold the SCENE 1 and
OFF buttons until scene LEDs stop cycling.
Circuit Selector Display
A11-A18
A21-A28
A31-A38
A21-A28
A31-A38
A41-A48
.
.
.
.
A61-A68
A71-A78
A81-A88
GRAFIK Eye